Goodrive300
inverters Basic operation instruction
171
Function
code
Name
Detailed instruction of parameters
Default
value
P12.18
Rated voltage of
synchronous motor 2
0~1200V
Depend
on model
P12.19
Rated current of
synchronous motor 2
0.8~6000.0A
Depend
on model
P12.20
Stator resistor of
synchronous motor 2
0.001~65.535Ω
Depend
on model
P12.21
Direct axis inductance of
synchronous motor 2
0.1~6553.5mH
Depend
on model
P12.22
Quadrature axis
inductance of
synchronous motor 2
0.1~6553.5mH
Depend
on model
P12.23
Back EMF constant of
synchronous motor 2
0~10000
300
7.7 Start-up and stop control
The start-up and stop control of the inverter includes three states: start after the running command
during normal powering on, start after the restarting function becomes valid during normal
powering on and start after the automatic fault reset. Below is the detailed instruction for three
startings.
There are three starting methods for the inverter: start from the starting frequency directly, start
after the AC braking and start after the rotation speed tracking. The user can select according to
different situations to meet their needs.
For the load with big inertia, especially in the cases where the reverse rotation may occur, it is
better to select starting after DC braking and then starting after rotation speed tracking.
Note: it is recommended to use the direct starting to drive synchronous motor.
1. The starting logic figure of starting after the running command during the normal powering on
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...