Goodrive300
inverters Function codes
57
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
1: Reserved
P01.06
Reserved
Reserv
ed
◎
P01.07
Reserved
Reserv
ed
◎
P01.08 Stop mode
0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to
decrease the output frequency during the set time.
When the frequency decreases to P01.15, the
inverter stops.
1: Coast to stop: after the stop command becomes
valid, the inverter ceases the output immediately.
And the load coasts to stop at the mechanical
inertia.
0
○
P01.09
Starting
frequency
of DC
braking
0.00Hz
○
P01.10
Waiting
time of DC
braking
0.00s
○
P01.11
DC braking
current
0.0%
○
P01.12 DC braking
The starting frequency of stop braking: the inverter
will carry on stop DC braking when the frequency is
arrived during the procedure of decelerating to
stop.
The waiting time of stop braking: before the stop
DC braking, the inverter will close output and begin
to carry on the DC braking after the waiting time.
This function is used to avoid the overcurrent fault
caused by DC braking when the speed is too high.
Stop DC braking current: the DC brake added. The
stronger the current, the bigger the DC braking
0.0s
○
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...