Goodrive300
inverters Basic operation instruction
165
Function
code
Name
Detailed instruction of parameters
Default
value
frequency
8:Ethernet communication setting upper-limit
frequency
9: Reserved
P03.16
Keypad setting for
upper frequency of
forward rotation
0.00Hz~P00.03 (the Max. frequency)
50.00 Hz
P03.17
Keypad setting for
upper frequency of
reverse rotation
0.00 Hz~P00.03 (the Max. frequency)
50.00 Hz
P03.18
Upper
electromotion
torque
source
0
P03.19
Upper braking
torque
source
0:Keypad setting upper-limit frequency(P03.20
sets P03.18, P03.21 sets P03.19)
1: AI1
2: AI2
3: AI3
4: HDI
5:MODBUS communication
6:PROFIBUS communication
7:Ethernet communication
8: Reserved
0
P03.20
Keypad setting of
electromotion
torque
0.0~300.0%( rated current of the motor)
180.0%
P03.21
Keypad setting of
braking torque
0.0~300.0%( rated current of the motor)
180.0%
P17.09
Output torque
-250.0~250.0%
0.0%
P17.15
Torque reference
-300.0~300.0%( rated current of the motor)
7.6 Parmeters of the motor
Physical accident may occur if the motor starts up suddenly during autotune.
Please check the safety of surrounding environment of the motor and the
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...