Goodrive300
inverters Basic operation instruction
179
Relative parameters list:
Function
code
Name
Detailed instruction of parameters
Default
value
P00.03
Max. output frequency
P00.04~400.00Hz
50.00Hz
P00.04
Upper limit of the running
frequency
P00.05~P00.03
50.00Hz
P00.05
Lower limit of the running
frequency
0.00Hz~P00.04
0.00Hz
P00.06
A frequency command
0
P00.07
B frequency command
0:Keypad
1: AI1
2: AI2
3: AI3
4:High-speed pulse HDI setting
5:Simple PLC program setting
6: Multi-step speed running setting
7: PID control setting
8:MODBUS communication setting
9:PROFIBUS communication setting
10:Ethernet communication
setting(reserved)
11:Reserved
1
P00.08
B frequency command
reference
0: Maximum output frequency
1:A frequency command
0
P00.09
Combination of the setting
source
0:A
1:B
2:(A+B)combination
3:(A-B)combination
4:Max(A,B)combination
5:Min(A,B)combination
0
P05.01~P0
5.09
Multi-function digital input
terminals
(S1~S8,HDI) function
selection
10:Increasing frequency setting (UP)
11:Decreasing frequency setting
(DOWN)
12:Cancel the frequency change setting
13:Shift between A setting and B setting
14:Shift between combination setting
and A setting
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...