Goodrive300
inverters Appendix D
294
Recommended
cable size (mm
2
)
Connecting cable size (mm
2
)
Model
RST
UVW
PE
RST
UVW
P1,(+)
PB
(+),(-)
PE
Terminal
screw
Tightening
torque
(Nm)
GD300-5R5G-4
2.5
2.5
2.5~16
4~16
4~6
2.5~6
M4
1.2~1.5
GD300-7R5G-4
4
4
2.5~16
4~16
4~6
2.5~6
M5
2-~2.5
GD300-011G-4
6
6
6~16
6~16
6~10
6~10
M5
2-~2.5
GD300-015G-4
10
10
10~16
6~16
6~10
6~16
M5
2-~2.5
GD300-018G-4
16
16
16~25 16~25
6~10
10~16
M5
2-~2.5
GD300-022G-4
16
16
10~16 16~35 10~16
10~16
M6
4~6
GD300-030G-4
25
16
16~25 16~35 16~25
16~25
M6
4~6
GD300-037G-4
25
16
25~50 25~50 16~50
16~25
M8
9~11
GD300-045G-4
35
16
25~50 25~50 25~50
16~25
M8
9~11
GD300-055G-4
50
25
35~95 50~95 25~95
25
M8
9~11
GD300-075G-4
70
35
70~95 35~95 50~75
25~35
M10
18~23
GD300-090G-4
95
50
35~95
35~150 25~70 50~150
M10
18~23
GD300-110G-4
120
70
95~300 70~300 35~300 70~240
M10
18~23
GD300-132G-4
185
95
95~300 70~300 35~300 95~240
GD300-160G-4
240
120
95~300 95~300 70~300 120~240
GD300-200G-4
95*2P
95
95~150 70~150 70~150 35~95
GD300-220G-4
150*2P
150
95~150 70~150 70~150 50~150
GD300-250G-4
95*4P
95*2P
95~150 70~150 70~150 60~150
GD300-280G-4
95*4P
95*2P
95~150 70~150 70~150 70~150
GD300-315G-4
95*4P
95*4P
95~150 70~150 70~150 70~150
GD300-350G-4
95*4P
95*4P
95~150 70~150 70~150 70~150
GD300-400G-4
150*4P
150*2P
95~150 70~150 70~150 70~150
GD300-500G-4
150*4P
150*2P
95~150 70~150 70~150 70~150
It is recommended to
use wrench or
sleeve because
screw is used as
terminal.
Note:
1. It is appropriate to use the recommended cable size under 40
℃
and rated current. The
wiring distance should be no more than 100m..
2. Terminals P1, (+), PB and (-) connects the DC reactor options and parts.
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...