Goodrive300
inverters Function codes
70
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
Note: Setting modes 2~10, 100% corresponds to
three times of the rated current of the motor.
P03.12
Keypad
setting
torque
Setting range: -300.0%~300.0%(rated current of
the motor)
50.0%
○
P03.13
Torque
reference
filter time
0.000~10.000s
0.010s
○
P03.14
Upper
frequency
of forward
rotation in
vector
control
0
○
P03.15
Upper
frequency
of reverse
rotation in
vector
control
0:Keypad (P03.16 sets P03.14,P03.17 sets
P03.15)
1: AI1
2: AI2
3: AI3
4:Pulse frequency HDI setting upper-limit
frequency
5:Multi-step setting upper-limit frequency
6:MODBUS communication setting upper-limit
frequency
7:PROFIBUS communication setting upper-limit
frequency
8:Ethernet communication setting upper-limit
frequency
9: Reserved
Note:setting method 1~9, 100% corresponds to the
maximum frequency
0
○
P03.16
Keypad
setting for
upper
frequency
of forward
rotation
This function is used to set the upper limit of the
frequency. P03.16 sets the value of P03.14; P03.17
sets the value of P03.15.
Setting range:0.00 Hz~P00.03 (the Max. output
frequency)
50.00
Hz
○
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...