Goodrive300
inverters Function codes
131
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
s motor 2
P12.20
Stator
resistor of
synchronou
s motor 2
0.001~65.535Ω
configure the motor
according to the
standard principles, if
the gap between the
motor and the
standard one is huge,
the features of the
inverter will decrease.
Note: reset the rated
power of the
motor(P12.15),initializ
e the motor parameter
of P12.16~ P12.19.
Depend
on
model
○
P12.21
Direct axis
inductance
of
synchronou
s motor 2
0.1~6553.5mH
Depend
on
model
○
P12.22
Quadrature
axis
inductance
of
synchronou
s motor 2
0.1~6553.5mH
Depend
on
model
○
P12.23
Back EMF
constant of
synchronou
s motor 2
When P00.15=2, the set
value of P12.23 cannot be
updated by autotuning,
please count according to
the following method.
The counter-electromotive
force constant can be
counted according to the
After finish the motor
parameter autotuning,
the set value of
P12.20~P12.22 will
renew automatically.
These parameters are
basic parameters
controlled by vectors
which directly impact
the features.
When P00.15=1, the
set value of P12.23
can be updated
through autotuning
automatically, and
there is no need to
change the value of
P12.23; when
P00.15=2, the set
300
○
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...