Goodrive300
inverters Appendix A
272
Bit 15~00
Parameter value (high word) or return error
code value
00
The fourth word PKW4 (16 bit)
Bit 15~00
Parameter value (low word)
0~65535
Note: If the master requests one parameter value, the value of PKW3 and PKW4 will not be
valid.
Task requests and responses
When passing data to slave machine, master machine use request label while slave
machine use response label to positive or negative confirmation. Table 5.5 and Table 5.6 list
the request/response functional.
The definition of task logo PKW1 is as follows:
Definition of task logo PKW1
Request label (From master to slave)
Response label
Request
Function
Positive
confirmation
Negative
confirmation
0
No task
0
-
1
Request parameter value
1,2
3
2
Modification parameter value (one word)
[only change RAM]
1
3 or 4
3
Modification parameter value (double word)
[only change RAM]
2
3 or 4
4
Modification parameter value (one word)
[RAM and EEPROM are modified]
1
3 or 4
5
Modification parameter value (double word)
[RAM and EEPROM are modified]
2
3 or 4
Request label
"2"-modification parameter value (one word) [only change RAM],
"3"-modification parameter value (double word) [only change RAM]
"5"-modification parameter value (double word) [RAM and EPROM are modified] not support
currently.
Reponses logo PKW1 defines as below:
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...