![INVT GD300-004G-4 Operation Manual Download Page 223](http://html1.mh-extra.com/html/invt/gd300-004g-4/gd300-004g-4_operation-manual_2085739223.webp)
Goodrive300
inverters Fault tracking
222
CE
485
communicatio
n fault
The baud rate setting is
incorrect.
Fault occurs to the
communication wiring.
The communication address
is wrong.
There is strong interference
to the communication.
Set proper baud rate
Check the communication
connection distribution
Set proper communication
address.
Chang or replace the connection
distribution or improve the
anti-interference capability.
ItE
Current-detect
ing fault
The connection of the control
board is not good
Assistant power is bad
Hoare components is broken
The modifying circuit is
abnormal.
Check the connector and
repatch
Change the Hoare
Change the main control panel
tE
Motor-autotun
ing fault
The motor capacity does not
comply with the inverter
capability
The rated parameter of the
motor does not set correctly.
The offset between the
parameters from autotune
and the standard parameter
is huge
Autotune overtime
Change the inverter mode
Set the ratedparameter
according to the motor name
plate
Empty the motor load and
reindentify
Check the motor connection and
set the parameter.
Check if the upper limit
frequency is above 2/3 of the
rated frequency.
EEP
EEPROM
operation fault
Error of controlling the write
and read of the parameters
Damage to EEPROM
Press STOP/RST to reset
Change the main control panel
PIDE
PID feedback
outline fault
PID feedback offline
PID feedback source
disappear
Check the PID feedback signal
Check the PID feedback source
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...