Goodrive300
inverters Function codes
51
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
current running frequency.
The multi-step speed has the priority when P00.06
or P00.07 does not equal to 6, but the setting stage
can only be the 1~15 stage. The setting stage is
1~15 if P00.06 or P00.07 equals to 6.
7: PID control setting
The running mode of the inverter is process PID
control when P00.06=7 or P00.07=7. It is
necessary to set P09. The running frequency of the
inverter is the value after PID effect. See P09 for
the detailed information of the given source, given
value, feedback source of PID.
8:MODBUS communication setting
The frequency is set by MODBUS communication.
See P14 for detailed information.
9:PROFIBUS communication setting
The frequency is set by PROFIBUS
communication. See P15 for the detailed
information.
10:Ethernet communication setting(reserved)
11:Reserved
Note:A frequency and B frequency can not set as
the same frequency given method.
P00.08
B
frequency
command
reference
0:Maximum output frequency, 100% of
B frequency setting corresponds to the maximum
output frequency
1:A frequency command, 100% of B frequency
setting corresponds to the maximum output
frequency. Select this setting if it needs to adjust on
the base of A frequency command.
0
○
P00.09
Combinatio
n of the
setting
0: A, the current frequency setting is A freauency
command
1: B, the current frequency setting is B frequency
0
○
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...