Goodrive300
inverters Function codes
49
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P00.03
Max. output
frequency
This parameter is used to set the maximum output
frequency of the inverter. Users should pay
attention to this parameter because it is the
foundation of the frequency setting and the speed
of acceleration and deceleration.
Setting range: P00.04~400.00Hz
50.00H
z
◎
P00.04
Upper limit
of the
running
frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the inverter
which is lower than or equal to the maximum
frequency.
Setting range:P00.05~P00.03 (Max. output
frequency)
50.00H
z
◎
P00.05
Lower limit
of the
running
frequency
The lower limit of the running frequency is that of
the output frequency of the inverter.
The inverter runs at the lower limit frequency if the
set frequency is lower than the lower limit one.
Note:
Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range:0.00Hz~P00.04 (Upper limit of the
running frequency)
0.00Hz
◎
P00.06
A
frequency
command
0
○
P00.07
B
frequency
command
0:Keypad
Modify the value P00.10 (set the frequency by
keypad) to modify the frequency by the keypad.
1: AI1
2: AI2
3: AI3
Set the frequency by analog input terminals.
Goodrive300 series inverters provide 3 ways
analog input terminals as the standard
configuration, of which AI1/AI2 are the
voltage/current option (0~10V/0~20mA) which can
be shifted by jumpers; while AI3 is voltage input
(-10V~+10V).
2
○
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...