Goodrive300
inverters Basic operation instruction
211
Function code
Name
Detailed instruction of parameters
Default
value
P00.03
Max. output
frequency
P00.03~400.00Hz
50.00Hz
P00.06
A frequency
command
0:Keypad
1: AI1
2: AI2
3: AI3
4:High-speed pulse HDI setting
5:Simple PLC program setting
6: Multi-step speed running setting
7: PID control setting
8:MODBUS communication setting
9:PROFIBUS communication setting
10:Ethernet communication
setting(reserved)
11:Reserved
0
P00.11
ACC time 1
0.0~3600.0s
Depend
on
model
P00.12
DEC time 1
0.0~3600.0s
Depend
on
model
P05.01~P05.09
Digital input
function
selection
26:Traverse Pause(stop at the current
frequency)
27:Traverse reset(return to the center
frequency)
P08.15
Traverse range
0.0~100.0%(relative to the set frequency)
0.0%
P08.16
Sudden jumping
frequency range
0.0~50.0%(relative to the traverse range)
0.0%
P08.17
Traverse boost
time
0.1~3600.0s
5.0s
P08.18
Traverse
declining time
0.1~3600.0s
5.0s
7.17 Pulse counter
Goodrive300 series inverters support pulse counter which can input counting pulse through HDI
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...