![INVT GD300-004G-4 Operation Manual Download Page 294](http://html1.mh-extra.com/html/invt/gd300-004g-4/gd300-004g-4_operation-manual_2085739294.webp)
Goodrive300
inverters Appendix D
293
D.4.2 Control cables
All analog control cables and the cable used for the frequency input must be shielded. Use a
double-shielded twisted pair cable (Figure a) for analog signals. Employ one individually
shielded pair for each signal. Do not use common return for different analog signals.
A double-shielded cable is the best alternative for low-voltage digital signals, but a
single-shielded or unshielded twisted multipair cable (Fig b) is also usable. However, for
frequency input, always use a shielded cable.
Note: Run analog and digital signals in separate cables.
The relay cable needs the cable type with braided metallic screen.
The keypad needs to connect with cables. It is recommended to use the screen cable on
complex electrical magnetic condition.
Do not make any voltage tolerance or insulation resistance tests (for example hi-pot or
megger) on any part of the drive as testing can damage the drive. Every drive has been
tested for insulation between the main circuit and the chassis at the factory. Also, there are
voltage-limiting circuits inside the drive which cut down the testing voltage automatically.
Check the insulation of the input power cable according to local regulations before
connecting to the drive.
D.4.2.1 The inverters of AC 3PH 380V(-15%)~440V(+10%)
Recommended
cable size (mm
2
)
Connecting cable size (mm
2
)
Model
RST
UVW
PE
RST
UVW
P1,(+)
PB
(+),(-)
PE
Terminal
screw
Tightening
torque
(Nm)
GD300-1R5G-4
2.5
2.5
2.5~6
2.5~6
2.5~6
2.5~6
M4
1.2~1.5
GD300-2R2G-4
2.5
2.5
2.5~6
2.5~6
2.5~6
2.5~6
M4
1.2~1.5
GD300-004G-4
2.5
2.5
2.5~6
2.5~6
2.5~6
2.5~6
M4
1.2~1.5
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...