Goodrive300
inverters Basic operation instruction
191
Set
value
Function
Instructions
22
ACC/DEC time selection 2
terminals.
Terminal
1
Terminal
2
ACC/DEC time
selection
Corresponding
parameter
OFF
OFF
ACC/DEC time 1 P00.11/P00.12
ON
OFF
ACC/DEC time 2 P08.00/P08.01
OFF
ON
ACC/DEC time 3 P08.02/P08.03
ON
ON
ACC/DEC time 4 P08.04/P08.05
23
Simple PLC stop reset
Restart simple PLC and clear the memory state of
PLC.
24
Simple PLC pause
Program pause during PLC implement. Run at the
current speed stage. After cancel the function, simple
PLC continues to run.
25
PID control pause
Temporal PID invalid and the inverter will output at the
current frequency.
26
Traverse pause (stop at the
current frequency)
The inverter will stop at the current output and after
canceling the function, the inverter will continue to
traverse run at the current frequency.
27
Traverse reset (return to the
middle frequency)
The setting frequency of the inverter will come back to
the middle frequency.
28
Counter reset
Counter clear
29
Torque control disabling
The inverter shifts from torque control mode to speed
control mode.
30
ACC/DEC disabling
Ensure the inverter will not be affected by the external
signals (except for the stopping command) and keep
the current output frequency.
31
Counter trigging
Enable the pulse counter.
32
Length reset
Length counter clear
33
Frequency
increasing/decreasing setting
temporal clear
When the terminal closes, the frequency set by
UP/DOWN can be cleared. All set frequency will be
restored into the given frequency by the frequency
command channel and the frequency will come back
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...