Goodrive300
inverters Function codes
110
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P08.40
PWM
selection
0x00~0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1:Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at
low speed
2: No limit
01
◎
P08.41
Over
commissio
n selection
LED ones
0: Invalid
1: Valid
LED tens (for factory commissioning)
0: Light overcommission; in zone 1
1: Heavy overcommission; in zone 2
1
◎
P08.42
Keypad
data control
0x000~0x1223
LED ones:frequency enable selection
0:Both
∧
/
∨
keys and digital potentiometer
adjustments are valid
1:Only
∧
/
∨
keys adjustment is valid
2:Only digital potentiometer adjustments is valid
3:Neither
∧
/
∨
keys nor digital potentiometer
adjustments are valid
LED tens: frequency control selection
0:Only valid when P00.06=0 or P00.07=0
1:Valid for all frequency setting manner
2:Invalid for multi-step speed when multi-step
0x0000
○
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...