MAP 0440: Short in 48 Volts DC Power Distribution
MAP 0440: Short in 48 V dc Power Distribution
Short in 48 V dc distribution system. Refer to Figure 1-26 for a diagram of the RS/6000 SP frame 48 volt
distribution.
001
Short in 48 V dc power distribution.
J1
P1
J2 P2
J3 P3
J4
P4
J5 P5
Switch
J407
Frame Connector Card
N+1
Power
Supplies
BUS
Bars
A
B
C
D
CB
CB
CB
CB
RISC
RISC
I/O Planar
-12 +12 +5v
I/O Planar
-12 +12 +5v
Node
Power
Supply
Node
Power
Supply
Node 4
Node 16
Nodes
9 10 11
Nodes
13 14 15
Nodes
1 2 3
Nodes
5 6 7
12
8
Figure
1-26. PDU 48 Volts Distribution Diagram
– Switch all processor node and switch assembly circuit breakers to Off (‘0’) position.
– Disconnect dc distribution cables PDU-BH-P1, PDU-BH-P2, PDU-BH-P3, PDU-BH-P4, and PDU-BH-P5
at Power Distribution Unit. This isolates 48 V dc to the Power Distribution Unit only.
– Remove front skirt assembly and air filter bracket.
– Turn on all bulk power supplies from the control workstation.
– Check green LEDs on all bulk power supplies.
Are green LEDs lit on all bulk power supplies?
Yes No
002
dc short detected in the Power Distribution Unit section.
DANGER
High voltage present. Perform “Lockout/Tagout Procedure for PDU” on page 1-2 or
“Lockout/Bagout Procedure for PDU” on page 1-3 to remove primary power to the
frame.
Chapter 1. Maintenance Analysis Procedures (MAPs)
1-257
Summary of Contents for RS/6000 SP
Page 1: ...RS 6000 SP IBM Maintenance Information Volume 2 Maintenance Analysis Procedures GA22 7376 01...
Page 2: ......
Page 3: ...RS 6000 SP IBM Maintenance Information Volume 2 Maintenance Analysis Procedures GA22 7376 01...
Page 8: ...vi RS 6000 SP MAPs...
Page 10: ...viii RS 6000 SP MAPs...
Page 16: ...xiv RS 6000 SP MAPs...
Page 20: ...xviii RS 6000 SP MAPs...
Page 60: ...MAP 0130 Processor Node Figure 1 7 Thin Node High Level Diagram 1 40 RS 6000 SP MAPs...
Page 383: ......
Page 387: ......