MAP 0450: Frame Environment
MAP 0450: Frame Environment
Problem indicated by frame supervisor.
Pri-
ority
Condition
Action
1
Frame supervisor green LED #2 (dc OK) is
flashing.
Go to Step 001.
2
Frame temperature indicates over 40° C.
Go to Step 008 on page 1-264.
001
Frame 48 V dc voltage out of range.
DANGER
High energy present. Do not short 48 V to frame or 48 VRtn. Shorting will result in system
outage and possible physical injury.
– Remove rear panel of PDU dc section.
– Unplug the 48 V dc sense cable PDU-FC-P407 at connector card.
– Using a multimeter, measure the dc voltage between PDU-FC-P407 pin 1 and pin 3.
– Replug the 48 V dc sense cable PDU-FC-P407 at connector card.
Is the measured voltage in the range 44-52 V dc?
Yes No
002
DANGER
High voltage present. Perform “Lockout/Tagout Procedure for PDU” on page 1-2 or
“Lockout/Bagout Procedure for PDU” on page 1-3 to remove all power to the frame.
– Replace the 48 V dc sense cable PDU-FC-P407.
– Reconnect ac power and power on system.
– Go to “MAP 0570: End of Call” on page 1-357.
003
– Use the following prioritized table to continue service:
1-262
RS/6000 SP MAPs
Summary of Contents for RS/6000 SP
Page 1: ...RS 6000 SP IBM Maintenance Information Volume 2 Maintenance Analysis Procedures GA22 7376 01...
Page 2: ......
Page 3: ...RS 6000 SP IBM Maintenance Information Volume 2 Maintenance Analysis Procedures GA22 7376 01...
Page 8: ...vi RS 6000 SP MAPs...
Page 10: ...viii RS 6000 SP MAPs...
Page 16: ...xiv RS 6000 SP MAPs...
Page 20: ...xviii RS 6000 SP MAPs...
Page 60: ...MAP 0130 Processor Node Figure 1 7 Thin Node High Level Diagram 1 40 RS 6000 SP MAPs...
Page 383: ......
Page 387: ......