Reference Code
Description/Action Perform all actions before exchanging Failing Items
Failing Item
9310
Licensed Internal Code for the tape unit is not correct
9320
Tape device Licensed Internal Code failure
Do the following:
1.
Take a dump of the tape device Licensed Internal Code (see the 3490
Tape Drive service information).
2.
Power off the tape unit. Then power on the tape unit to resume
operation.
9350
Tape unit detected a read or write error on tape medium
A permanent read or write error occurred, and the tape unit determined
that the tape cartridge is defective. Exchange the tape cartridge.
MHKTMED
UHKCLN
FI00851
9351
I/O processor Licensed Internal Code error
If the system is operational, take a dump of the I/O processor data. For
more information, see the
iSeries Service Functions
information or ask your
next level of support for assistance.
9355
The data format is incorrect; the tape cannot be read
The tape device does not give support to the data format on the tape
cartridge. Re-initialize the tape cartridge or use a different tape cartridge.
MHKTMED
UHKCLN
FI00851
9500
I/O processor Licensed Internal Code error
If the system is operational, take a dump of the I/O processor data. For
more information, see the
iSeries Service Functions
information or ask your
next level of support for assistance.
96xx
Tape unit failure
Use online problem analysis and the 3490 Tape Unit service information to
continue analyzing the problem.
9800 to 9803
I/O processor successfully recovered from temporary error
No action required. This reference code is logged for information only.
9810
Problem analysis has determined a part should be replaced.
This reference code is used for ending Online Problem Analysis with a list
of failing items. (Information Only)
9899
Problem analysis completed, the problem has been corrected.
This reference code is used for ending Online Problem Analysis when no
problem was found or the problem was corrected.
UHKFIXD
9900
Licensed Internal Code for tape unit was not upgraded
The I/O processor loading of Licensed Internal Code (LIC) to the
programmable tape unit was not completed.
The tape unit will continue to operate with the previous LIC. You may do
either of the following:
v
Wait for next IPL when the system will attempt to load the LIC for the
tape unit again.
v
Perform TU-PIP4 to reset the IOP and the tape unit. When the IOP is
reset, if the device has the wrong level of LIC, the IOP will attempt to
load the new LIC.
3490
160
iSeries: iSeries 270, 800, 810, 820, 825, 830, 840, 870, 890, SB2, and SB3 Analyze Hardware Problems (System Reference
Codes)