11
11. Regarding Battery-less Absolute Type Actuator
1) For the pulse motor type, the setting switched over between the absolute type and
incremental type with the parameters.
y
Parameter No.83 Absorber unit
0 : not used = (Incremental Type), 1 : Use = (Absolute Type)
2) For actuator of RCP5 series, for the first time to turn the servo on after turning on the power,
it will have slight position adjustment due to the characteristics of the stepping motor.
The maximum movement amount at position adjustment operation is the distance of 0.025 ×
lead length [mm].
Also, the current position displayed on the teaching tool before turning the servo on is the
coordinates before adjustment operation.
3) After the first time the servo is tuned on after the power has been supplied, the home-return
complete signal [HEND] and the limit switch output signal (LS) are output.
4) When the first servo-on is conducted out of the soft limit range, an error would not be output.
Soft limit monitoring starts after it is moved into the range.
5) Make sure to have a home-return operation (absolute reset) after detaching the motor unit
from the actuator for motor replacement purpose and so on.
12. Motor Features in AUTO Mode
Status (condition) display and servomotor are available in AUTO Mode.
However, they are not available when the connection is established with SSCNET
Ⅲ
/H,
MECHATROLINK-
Ⅲ
or EtherCat Motion.
Summary of Contents for MCON-C
Page 1: ...MCON C CG Controller Instruction Manual Fourth Edition ...
Page 2: ......
Page 48: ...38 Chapter 1 Specifications Check ...
Page 268: ...258 3 10 Fieldbus Status LEDs ...
Page 274: ...264 Chapter 4 Vibration Suppress Control Function ...
Page 278: ...268 Chapter 5 Collision Detection Feature ...
Page 284: ...274 Chapter 6 Power saving Function ...
Page 292: ...282 Chapter 7 Absolute Reset and Absolute Battery ...
Page 358: ...348 Chapter 9 Troubleshooting ...
Page 474: ...Chapter 10 Appendix 464 ...
Page 478: ......
Page 479: ......