GE Power Management
745 Transformer Management Relay
5-45
5 SETPOINTS
5.6 S4 ELEMENTS
5
5.6 S4 ELEMENTS
5.6.1 DESCRIPTION
Protection and monitoring elements are configured in this page. This includes: complete differential protection;
phase, neutral, ground, negative sequence overcurrent protection; restricted ground fault (differential ground)
protection; under, over, and rate-of-change of frequency; overexcitation; harmonic monitoring; analog input
monitoring; current demand monitoring; and transformer overload monitoring.
5.6.2 INTRODUCTION TO ELEMENTS
Each element is comprised of a number of setpoints, some of which are common to all elements. These com-
mon setpoints are described below, avoiding repeated descriptions throughout this section:
yy
SETPOINTS
yy
S4 ELEMENTS
This message indicates the start of setpoints page
S4 ELEMENTS
. Press
to view the contents of this page, or
to go to the next page.
<NAME OF ELEMENT>
FUNCTION: Enabled
Range: Disabled / Enabled
Select
Enabled
to enable the element. For critical protection elements, this
setpoint will normally be set to
Enabled
except for test purposes. For elements
which are not to be used, this setpoint should be set to
Disabled
.
<NAME OF ELEMENT>
TARGET: Latched
Range: Self-reset / Latched / None
Target messages (accessed by the
key) indicate which elements
have picked up or operated. Select
Latched
to keep the element target
message in the queue of target messages, even after the condition which
caused the element to operate has been cleared, until a reset command is
issued. Select
Self-reset
to automatically remove the target message from the
queue of messages after the condition has been cleared. Select
None
to
inhibit the display of the target message when the element operates. Thus an
element whose “target type” is
None
will never disable the LED self-test feature
because can not generate a displayable target message.
<NAME OF ELEMENT>
BLOCK: Disabled
Range: Disabled / Logc Inpt 1 (2-16) / Virt Inpt 1 (2-16) / Output Rly 1 (2-8) /
SelfTest Rly / Virt Outpt 1 (2-5)
Select any logic input, virtual input, output relay, or virtual output which,
when asserted or operated, will block the element from operating. Selecting
a logic input or virtual input allows the element to be blocked based on a
decision external to the 745. Selecting an output relay or virtual output
allows the element to be blocked based on conditions detected by the 745
and the combination of logic programmed in the associated FlexLogic™
equation.
M E SSA G E
S ET PO INT
N EX T
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...