GE Power Management
745 Transformer Management Relay
8-83
8 COMMUNICATIONS
8.3 MODBUS MEMORY MAP
8
0000 0010
2 = Output Relay 3
0000 0011
3 = Output Relay 4
0000 0100
4 = Output Relay 5
0000 0101
5 = Output Relay 6
0000 0110
6 = Output Relay 7
0000 0111
7 = Output Relay 8
0000 1000
8 = Self-Test Relay
0000 1110 xxxx xxxx
Token = Virtual Output Operated
0000 0000
0 = Virtual Output 1
0000 0001
1 = Virtual Output 2
0000 0010
2 = Virtual Output 3
0000 0011
3 = Virtual Output 4
0000 0100
4 = Virtual Output 5
0000 1111 xxxx xxxx
Token = Timer Operated
0000 0000
0 = Timer 1
0000 0001
1 = Timer 2
0000 0010
2 = Timer 3
0000 0011
3 = Timer 4
0000 0100
4 = Timer 5
0000 0101
5 = Timer 6
0000 0110
6 = Timer 7
0000 0111
7 = Timer 8
0000 1000
8 = Timer 9
0000 1001
9 = Timer 10
F48
16 bits
SIMULATION FUNCTION
0000 0000 0000 0000 0 = Disabled
0000 0000 0000 0001 1 = Prefault Mode
0000 0000 0000 0010 2 = Fault Mode
0000 0000 0000 0011 3 = Playback Mode
F49
16 bits
INPUT STATES
xxxx xxxx xxxx xxx1
Input 1 (0 = Open, 1 = Closed)
xxxx xxxx xxxx xx1x
Input 2 (0 = Open, 1 = Closed)
xxxx xxxx xxxx x1xx
Input 3 (0 = Open, 1 = Closed)
xxxx xxxx xxxx 1xxx
Input 4 (0 = Open, 1 = Closed)
xxxx xxxx xxx1 xxxx
Input 5 (0 = Open, 1 = Closed)
xxxx xxxx xx1x xxxx
Input 6 (0 = Open, 1 = Closed)
xxxx xxxx x1xx xxxx
Input 7 (0 = Open, 1 = Closed)
xxxx xxxx 1xxx xxxx
Input 8 (0 = Open, 1 = Closed)
xxxx xxx1 xxxx xxxx
Input 9 (0 = Open, 1 = Closed)
xxxx xx1x xxxx xxxx
Input 10 (0 = Open, 1 = Closed)
Table 8–7: 745 DATA FORMATS (Sheet 19 of 35)
FORMAT
CODE
APPLICABLE BITS
DEFINITION
xxxx x1xx xxxx xxxx
Input 11 (0 = Open, 1 = Closed)
xxxx 1xxx xxxx xxxx
Input 12 (0 = Open, 1 = Closed)
xxx1 xxxx xxxx xxxx
Input 13 (0 = Open, 1 = Closed)
xx1x xxxx xxxx xxxx
Input 14 (0 = Open, 1 = Closed)
x1xx xxxx xxxx xxxx
Input 15 (0 = Open, 1 = Closed)
1xxx xxxx xxxx xxxx
Input 16 (0 = Open, 1 = Closed)
F50
16 bits
OUTPUT RELAY STATES
xxxx xxxx xxxx xxx1
Output Relay 1
(0 = De-energized, 1 = Energized)
xxxx xxxx xxxx xx1x
Output Relay 2
(0 = De-energized, 1 = Energized)
xxxx xxxx xxxx x1xx
Output Relay 3
(0 = De-energized, 1 = Energized)
xxxx xxxx xxxx 1xxx
Output Relay 4
(0 = De-energized, 1 = Energized)
xxxx xxxx xxx1 xxxx
Output Relay 5
(0 = De-energized, 1 = Energized)
xxxx xxxx xx1x xxxx
Output Relay 6
(0 = De-energized, 1 = Energized)
xxxx xxxx x1xx xxxx
Output Relay 7
(0 = De-energized, 1 = Energized)
xxxx xxxx 1xxx xxxx
Output Relay 8
(0 = De-energized, 1 = Energized)
xxxx xxx1 xxxx xxxx
Self-Test Relay
(0 = De-energized, 1 = Energized)
F51
16 bits
DSP DIAGNOSTIC FLAGS
xxxx xxxx xxxx xxx1
A/D Virtual Ground
(0 = Okay, 1 = Out of Tolerance)
xxxx xxxx xxxx xx1x
A/D Subsystem
(0 = Okay, 1 = Not Responding)
F52
16 bits
LOGIC FLAG
xxxx xxxx xxxx xxx1
Pickup Flag
(0= Not Picked Up, 1= Picked Up)
xxxx xxxx xxxx xx1x
Operated Flag
(0 = Not Operated, 1 = Operated)
xxxx xxxx xxxx x1xx
Latched Flag
(0 = Not Latched, 1 = Latched)
xxxx xxxx xxxx 1xxx
Self test flag
(0= No error, 1= Error)
xxxx xxx1 xxxx xxxx
Phase A Flag
(0 = No Fault, 1 = Fault)
xxxx xx1x xxxx xxxx
Phase B Flag
(0 = No Fault, 1 = Fault)
xxxx x1xx xxxx xxxx
Phase C Flag
(0 = No Fault, 1 = Fault)
xxxx 1xxx xxxx xxxx
Ground Flag
(0 = No Fault, 1 = Fault)
Table 8–7: 745 DATA FORMATS (Sheet 20 of 35)
FORMAT
CODE
APPLICABLE BITS
DEFINITION
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...