GE Power Management
745 Transformer Management Relay
8-51
8 COMMUNICATIONS
8.3 MODBUS MEMORY MAP
8
201F
Reserved
INST
DIFFERENTIAL
2020
Inst Differential Function
---
---
---
F30
1 = Enabled
2021
Inst Differential Target
---
---
---
F46
1 = Latched
2022
Inst Differential Pickup
3.00 to 20.00
0.01
×
CT
F3
800 = 8.00
×
CT
2023
Inst Differential Block
---
---
---
F87
0 = Disabled
2024
Reserved
↓
↓
↓
↓
↓
↓
↓
203F
Reserved
WINDING 1
PHASE TIME
O/C
2040
Winding 1 Phase Time O/C Function
---
---
---
F30
1 = Enabled
2041
Winding 1 Phase Time O/C Target
---
---
---
F46
1 = Latched
2042
Winding 1 Phase Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
120 = 1.20
×
CT
2043
Winding 1 Phase Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2044
Winding 1 Phase Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2045
Winding 1 Phase Time O/C Reset
---
---
---
F68
1 = Linear
2046
Winding 1 Phase Time O/C Block
---
---
---
F87
0 = Disabled
2047
Winding 1 Harmonic Derating Correction
---
---
---
F30
0 = Disabled
2048
Reserved
↓
↓
↓
↓
↓
↓
↓
204F
Reserved
WINDING 2
PHASE TIME
O/C
2050
Winding 2 Phase Time O/C Function
---
---
---
F30
1 = Enabled
2051
Winding 2 Phase Time O/C Target
---
---
---
F46
1 = Latched
2052
Winding 2 Phase Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
120 = 1.20
×
CT
2053
Winding 2 Phase Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2054
Winding 2 Phase Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2055
Winding 2 Phase Time O/C Reset
---
---
---
F68
1 = Linear
2056
Winding 2 Phase Time O/C Block
---
---
---
F87
0 = Disabled
2057
Winding 2 Harmonic Derating Correction
---
---
---
F30
0 = Disabled
2058
Reserved
↓
↓
↓
↓
↓
↓
↓
205F
Reserved
WINDING 3
PHASE TIME
O/C
2060
Winding 3 Phase Time O/C Function
---
---
---
F30
1 = Enabled
2061
Winding 3 Phase Time O/C Target
---
---
---
F46
1 = Latched
2062
Winding 3 Phase Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
120 = 1.20
×
CT
2063
Winding 3 Phase Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2064
Winding 3 Phase Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2065
Winding 3 Phase Time O/C Reset
---
---
---
F68
1 = Linear
2066
Winding 3 Phase Time O/C Block
---
---
---
F87
0 = Disabled
2067
Winding 3 Harmonic Derating Correction
---
---
---
F30
0 = Disabled
Table 8–6: 745 MEMORY MAP (Sheet 35 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...