GE Power Management
745 Transformer Management Relay
5-59
5 SETPOINTS
5.6 S4 ELEMENTS
5
5.6.9 RESTRICTED GROUND (DIFFERENTIAL GROUND)
a) WINDING 1 (2/3) RESTRICTED GROUND FAULT
This section contains the settings to configure the restricted ground fault elements.
Figure 5–9: RESTRICTED EARTH GROUND FAULT PROTECTION
Restricted Ground Fault protection is often applied to transformers having impedance grounded wye windings.
It is intended to provide sensitive ground fault detection for low magnitude fault currents which would not be
detected by the percent differential element.
Figure 5–10: RESISTANCE GROUNDED WYE WINDING
y
RESTRICTED GROUND
y
[ENTER] for more
This message indicates the start of the
RESTRICTED GROUND
section. To
continue with these setpoints press
, or press
to go to the
next section.
E N T E R
M E SSA G E
87T
87T
87TG
87TG
Rg
Rg
Wye Winding
FAULT
I
F
Delta Winding
I
P
Impedance grounded
wye winding
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...