8-54
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
WINDING 3
NEUTRAL
TIME O/C
continued
20F5
Winding 3 Neutral Time O/C Reset
---
---
---
F68
1 = Linear
20F6
Winding 3 Neutral Time O/C Block
---
---
---
F87
0 = Disabled
20F7
Reserved
↓
↓
↓
↓
↓
↓
↓
20FF
Reserved
WINDING 1
NEUTRAL
INST O/C 1
2100
Winding 1 Neutral Inst O/C 1 Function
---
---
---
F30
1 = Enabled
2101
Winding 1 Neutral Inst O/C 1 Target
---
---
---
F46
1 = Latched
2102
Winding 1 Neutral Inst O/C 1 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2103
Winding 1 Neutral Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2104
Winding 1 Neutral Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2105
Reserved
↓
↓
↓
↓
↓
↓
↓
210F
Reserved
WINDING 2
NEUTRAL
INST O/C 1
2110
Winding 2 Neutral Inst O/C 1 Function
---
---
---
F30
0 = Disabled
2111
Winding 2 Neutral Inst O/C 1 Target
---
---
---
F46
1 = Latched
2112
Winding 2 Neutral Inst O/C 1 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2113
Winding 2 Neutral Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2114
Winding 2 Neutral Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2115
Reserved
↓
↓
↓
↓
↓
↓
↓
211F
Reserved
WINDING 3
NEUTRAL
INST O/C 1
2120
Winding 3 Neutral Inst O/C 1 Function
---
---
---
F30
0 = Disabled
2121
Winding 3 Neutral Inst O/C 1 Target
---
---
---
F46
1 = Latched
2122
Winding 3 Neutral Inst O/C 1 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2123
Winding 3 Neutral Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2124
Winding 3 Neutral Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2125
Reserved
↓
↓
↓
↓
↓
↓
↓
212F
Reserved
WINDING 1
NEUTRAL
INST O/C 2
2130
Winding 1 Neutral Inst O/C 2 Function
---
---
---
F30
0 = Disabled
2131
Winding 1 Neutral Inst O/C 2 Target
---
---
---
F46
1 = Latched
2132
Winding 1 Neutral Inst O/C 2 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2133
Winding 1 Neutral Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
2134
Winding 1 Neutral Inst O/C 2 Block
---
---
---
F87
0 = Disabled
2135
Reserved
↓
↓
↓
↓
↓
↓
↓
213F
Reserved
Table 8–6: 745 MEMORY MAP (Sheet 38 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...