8-92
745 Transformer Management Relay
GE Power Management
8.4 DNP COMMUNICATIONS
8
8.4 DNP COMMUNICATIONS
8.4.1 DEVICE PROFILE DOCUMENT
DNP 3.0
DEVICE PROFILE DOCUMENT
Vendor Name: General Electric Power Management Inc.
Device Name: 745 Transformer Management Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
p
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
Binary Input (Object 1, Variations 1 and 2)
Binary Output (Object 10, Variation 2)
Analog Input (Object 30, Variations 1, 2, 3 and 4)
Analog Input Change (Object 32, Variations 1, 2, 3 and 4)
Warm Restart (Function code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
p
None
p
Fixed
Configurable (Note 1)
Maximum Application Layer Re-tries:
None
p
Configurable
Requires Data Link Layer Confirmation:
p
Never
p
Always
p
Sometimes
Configurable (Note 1)
Requires Application Layer Confirmation:
p
Never
p
Always
When reporting Event Data
p
When sending multi-fragment responses
p
Sometimes
p
Configurable
Timeouts while waiting for:
Data Link Confirm
p
None
p
Fixed
p
Variable
Configurable (Note 1)
Complete Appl. Fragment
None
p
Fixed
p
Variable
p
Configurable
Application Confirm
None
p
Fixed
p
Variable
p
Configurable
Complete Appl. Response
None
p
Fixed
p
Variable
p
Configurable
Others:
(None)
S
S
S
S
S
S
S
S
S
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...