8-62
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
VOLTS-PER-
HERTZ 1
continued
2303
Volts-Per-Hertz 1 Pickup
1.00 to 4.00
0.01
V/Hz
F3
236 = 2.36 V/Hz
2304
Volts-Per-Hertz 1 Shape
---
---
---
F86
0 = Def. Time
2305
Volts-Per-Hertz 1 Delay
0.00 to 600.00
0.01
s
F3
200 = 2.00 s
2306
Volts-Per-Hertz 1 Reset
0.0 to 6000.0
0.1
s
F2
0.0 s
2307
Volts-Per-Hertz 1 Block
---
---
---
F87
0 = Disabled
2308
Reserved
↓
↓
↓
↓
↓
↓
↓
230F
Reserved
VOLTS-PER-
HERTZ 2
2310
Volts-Per-Hertz 2 Function
---
---
---
F30
0 = Disabled
2311
Volts-Per-Hertz 2 Target
---
---
---
F46
1 = Latched
2312
Volts-Per-Hertz 2 Min. Operating Voltage
0.10 to 0.99
0.01
x VT
F3
10 = 0.10 x VT
2313
Volts-Per-Hertz 2 Pickup
1.00 to 4.00
0.01
V/Hz
F3
214 = 2.14 V/Hz
2314
Volts-Per-Hertz 2 Shape
---
---
---
F86
0 = Def. Time
2315
Volts-Per-Hertz 2 Delay
0.00 to 600.00
0.01
s
F3
4500 = 45.00 s
2316
Volts-Per-Hertz 2 Reset
0.0 to 6000.0
0.1
s
F2
0.0 s
2317
Volts-Per-Hertz 2 Block
---
---
---
F87
0 = Disabled
2318
Reserved
↓
↓
↓
↓
↓
↓
↓
231F
Reserved
WINDING 1
THD LEVEL
2320
Winding 1 THD Level Function
---
---
---
F30
0 = Disabled
2321
Winding 1 THD Level Target
---
---
---
F46
0 = Self-reset
2322
Winding 1 THD Level Min. Operating Current
0.03 to 1.00
0.01
×
CT
F3
10 = 0.10
×
CT
2323
Winding 1 THD Level Pickup
0.1 to 50.0
0.1
% ƒo
F2
500 = 50.0%
2324
Winding 1 THD Level Delay
0 to 60000
1
s
F1
10 s
2325
Winding 1 THD Level Block
---
---
---
F87
0 = Disabled
2326
Reserved
↓
↓
↓
↓
↓
↓
↓
232F
Reserved
WINDING 2
THD LEVEL
2330
Winding 2 THD Level Function
---
---
---
F30
0 = Disabled
2331
Winding 2 THD Level Target
---
---
---
F46
0 = Self-reset
2332
Winding 2 THD Level Min. Operating Current
0.03 to 1.00
0.01
×
CT
F3
10 = 0.10
×
CT
2333
Winding 2 THD Level Pickup
0.1 to 50.0
0.1
% ƒo
F2
500 = 50.0%
2334
Winding 2 THD Level Delay
0 to 60000
1
s
F1
10 s
2335
Winding 2 THD Level Block
---
---
---
F87
0 = Disabled
2336
Reserved
↓
↓
↓
↓
↓
↓
↓
233F
Reserved
Table 8–6: 745 MEMORY MAP (Sheet 46 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...