8-22
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
WINDING 3
02A0
Winding 3 Phase A Current - Magnitude
---
---
A
F80
---
CURRENT
02A1
Winding 3 Phase A Current - Angle
0 to 359
1
° Lag
F1
---
02A2
Winding 3 Phase B Current - Magnitude
---
---
A
F80
---
02A3
Winding 3 Phase B Current - Angle
0 to 359
1
° Lag
F1
---
02A4
Winding 3 Phase C Current - Magnitude
---
---
A
F80
---
02A5
Winding 3 Phase C Current - Angle
0 to 359
1
° Lag
F1
---
02A6
Winding 3 Neutral Current - Magnitude
---
---
A
F80
---
02A7
Winding 3 Neutral Current - Angle
0 to 359
1
° Lag
F1
---
02A8
Winding 3 Ground Current - Magnitude
---
---
A
F83
---
02A9
Winding 3 Ground Current - Angle
0 to 359
1
° Lag
F1
---
02AA
Winding 3 Loading
0 to 999
1
% rated
F1
---
02AB
Winding 3 Ave. Phase Current
---
---
A
F80
---
02AC
Reserved
02AF
Reserved
SEQUENCE
CURRENTS
02B0
Winding 1 Positive Sequence Current Magnitude
---
---
A
F78
---
02B1
Winding 1 Positive Sequence Current Angle
0 to 359
1
° Lag
F1
---
02B2
Winding 2 Positive Sequence Current Magnitude
---
---
A
F79
---
02B3
Winding 2 Positive Sequence Current Angle
0 to 359
1
° Lag
F1
---
02B4
Winding 3 Positive Sequence Current Magnitude
---
---
A
F80
---
02B5
Winding 3 Positive Sequence Current Angle
0 to 359
1
° Lag
F1
---
02B6
Winding 1 Negative Sequence Current Magnitude
---
---
A
F78
---
02B7
Winding 1 Negative Sequence Current Angle
0 to 359
1
° Lag
F1
---
02B8
Winding 2 Negative Sequence Current Magnitude
---
---
A
F79
---
02B9
Winding 2 Negative Sequence Current Angle
0 to 359
1
° Lag
F1
---
02BA
Winding 3 Negative Sequence Current Magnitude
---
---
A
F80
---
02BB
Winding 3 Negative Sequence Current Angle
0 to 359
1
° Lag
F1
---
02BC
Winding 1 Zero Sequence Current Magnitude
---
---
A
F78
---
02BD
Winding 1 Zero Sequence Current Angle
0 to 359
1
° Lag
F1
---
02BE
Winding 2 Zero Sequence Current Magnitude
---
---
A
F79
---
02BF
Winding 2 Zero Sequence Current Angle
0 to 359
1
° Lag
F1
---
02C0
Winding 3 Zero Sequence Current Magnitude
---
---
A
F80
---
02C1
Winding 3 Zero Sequence Current Angle
0 to 359
1
° Lag
F1
---
02C2
Reserved
↓
↓
↓
↓
↓
↓
↓
02CF
Reserved
DIFFERENTIAL
CURRENT
02D0
Phase A Differential Current - Magnitude
0.00 to 655.35
0.01
x CT
F3
---
02D1
Phase A Differential Current - Angle
0 to 359
1
° Lag
F1
---
02D2
Phase B Differential Current - Magnitude
0.00 to 655.35
0.01
x CT
F3
---
Table 8–6: 745 MEMORY MAP (Sheet 6 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...