6 ACTUAL VALUES
6.4 A3 EVENT RECORDER
6
W3 (% ƒo) H5a: 0.0
H5b: 0.0 H5c: 0.0
This message displays the magnitude of the fifth harmonic current for each
phase of winding 3 at the moment of the event.
PHASE A DIFFERENTIAL
CURRENT: 0.00 x CT
This message displays the differential current for phase A at the moment of
the event.
PHASE B DIFFERENTIAL
CURRENT: 0.00 x CT
This message displays the differential current for phase B at the moment of
the event.
PHASE C DIFFERENTIAL
CURRENT: 0.00 x CT
This message displays the differential current for phase C at the moment of
the event.
PHASE A RESTRAINT
CURRENT: 0.00 x CT
This message displays the restraint current for phase A at the moment of the
event.
PHASE B RESTRAINT
CURRENT: 0.00 x CT
This message displays the restraint current for phase B at the moment of the
event.
PHASE C RESTRAINT
CURRENT: 0.00 x CT
This message displays the restraint current for phase C at the moment of the
event.
SYSTEM FREQUENCY:
0.00 Hz
This message displays the system frequency at the moment of the event.
FREQUENCY DECAY
RATE: 0.00 Hz/s
This message displays the frequency decay rate at the moment of the event.
TAP CHANGER
POSITION: n/a
This message displays the tap changer position at the moment of the event.
VOLTS-PER-HERTZ:
0.00 V/Hz
This message displays the volts-per-hertz at the moment of the event.
AMBIENT TEMPERATURE:
0°C
This message displays the ambient temperature at the moment of the event.
ANALOG INPUT:
0 µA
This message displays the measured analog input at the moment of the
event.
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...