8-56
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
WINDING 3
GROUND TIME
O/C
2180
Winding 3 Ground Time O/C Function
---
---
---
F30
0 = Disabled
2181
Winding 3 Ground Time O/C Target
---
---
---
F46
1 = Latched
2182
Winding 3 Ground Time O/C Pickup
0.05 to 20.00
0.01
x CT
F3
85 = 0.85 x CT
2183
Winding 3 Ground Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2184
Winding 3 Ground Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2185
Winding 3 Ground Time O/C Reset
---
---
---
F68
1 = Linear
2186
Winding 3 Ground Time O/C Block
---
---
---
F87
0 = Disabled
2187
Reserved
↓
↓
↓
↓
↓
↓
↓
218F
Reserved
WINDING 1
GROUND INST
O/C 1
2190
Winding 1 Ground Inst O/C 1 Function
---
---
---
F30
0 = Disabled
2191
Winding 1 Ground Inst O/C 1 Target
---
---
---
F46
1 = Latched
2192
Winding 1 Ground Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
2193
Winding 1 Ground Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2194
Winding 1 Ground Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2195
Reserved
↓
↓
↓
↓
↓
↓
↓
219F
Reserved
WINDING 2
GROUND INST
O/C 1
21A0
Winding 2 Ground Inst O/C 1 Function
---
---
---
F30
0 = Disabled
21A1
Winding 2 Ground Inst O/C 1 Target
---
---
---
F46
1 = Latched
21A2
Winding 2 Ground Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
21A3
Winding 2 Ground Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
21A4
Winding 2 Ground Inst O/C 1 Block
---
---
---
F87
0 = Disabled
21A5
Reserved
↓
↓
↓
↓
↓
↓
↓
21AF
Reserved
WINDING 3
GROUND INST
O/C 1
21B0
Winding 3 Ground Inst O/C 1 Function
---
---
---
F30
0 = Disabled
21B1
Winding 3 Ground Inst O/C 1 Target
---
---
---
F46
1 = Latched
21B2
Winding 3 Ground Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
21B3
Winding 3 Ground Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
21B4
Winding 3 Ground Inst O/C 1 Block
---
---
---
F87
0 = Disabled
21B5
Reserved
↓
↓
↓
↓
↓
↓
↓
21BF
Reserved
WINDING 1
GROUND INST
O/C 2
21C0
Winding 1 Ground Inst O/C 2 Function
---
---
---
F30
0 = Disabled
21C1
Winding 1 Ground Inst O/C 2 Target
---
---
---
F46
1 = Latched
21C2
Winding 1 Ground Inst O/C 2 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
21C3
Winding 1 Ground Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
Table 8–6: 745 MEMORY MAP (Sheet 40 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...