GE Power Management
745 Transformer Management Relay
11-17
11 SETPOINT TABLES
11.1 COMMISSIONING SUMMARY
11
Analog Level 1 Target
Self-reset
Analog Level 1 Pickup
10 mA
Analog Level 1 Delay
50 s
Analog Level 1 Block
Disabled
Analog Level 2 Function
Disabled
Analog Level 2 Target
Self-reset
Analog Level 2 Pickup
100 mA
Analog Level 2 Delay
100 s
Analog Level 2 Block
Disabled
CURRENT DEMAND
W1 Current Demand Function
Disabled
W1 Current Demand Target
Self-reset
W1 Current Demand Pickup
100 A
W1 Current Demand Block
Disabled
W2 Current Demand Function
Disabled
W2 Current Demand Target
Self-reset
W2 Current Demand Pickup
400 A
W2 Current Demand Block
Disabled
W3 Current Demand Function
Disabled
W3 Current Demand Target
Self-reset
W3 Current Demand Pickup
400 A
W3 Current Demand Block
Disabled
TRANSFORMER OVERLOAD
Xformer Overload Function
Disabled
Xformer Overload Target
Self-reset
Xformer Overload Pickup
208%
Xformer Overload Delay
10 s
Xformer Overload Block
Disabled
Overtemp Alarm Signal
Disabled
Tap changer failure
Tap changer failure Function
Disabled
Tap changer failure Target
Self-Reset
Tap changer failure Delay
5.0 s
Tap changer failure Block
Disabled
Table 11–6: S4 ELEMENTS (Sheet 12 of 12)
DESCRIPTION
DEFAULT
GROUP 1
GROUP 2
GROUP 3
GROUP 4
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...