GE Power Management
745 Transformer Management Relay
8-13
8 COMMUNICATIONS
8.2 MODBUS PROTOCOL
8
1.
First, preload the addresses listed in the first column of the table to in User Map Addresses #1 to #6
(addresses 0180 to 0185 hex).
2.
Now that the User Map Addresses have been setup, the required memory map locations can be accessed
via the User Map Values #1 to #6 (addresses 0100 to 0105 hex). Both actual values and setpoints may be
read.
Master Query Message:
Example (hex):
SLAVE ADDRESS
11
query message for slave 11
FUNCTION CODE
10
store multiple setpoint values
DATA STARTING ADDRESS: high order byte
01
data starting at address 0180
DATA STARTING ADDRESS: low order byte
80
NUMBER OF SETPOINTS: high order byte
00
6 setpoint values = 12 bytes total
NUMBER OF SETPOINTS: low order byte
06
BYTE COUNT
0C
12 bytes of data
DATA #1: high order byte
02
0200
→
Relay Status
DATA #1: low order byte
00
DATA #2: high order byte
02
0210
→
W3 Phase Time O/C Flag
DATA #2: low order byte
10
DATA #3: high order byte
03
0300
→
W1 Phase A 4th Harmonic Content
DATA #3: low order byte
00
DATA #4: high order byte
03
0301
→
W1 Phase B 4th Harmonic Content
DATA #4: low order byte
01
DATA #5: high order byte
03
0302
→
W1 Phase C 4th Harmonic Content
DATA #5: low order byte
02
DATA #6: high order byte
20
2002
→
Percent Differential Pickup
DATA #6: low order byte
02
CRC: low order byte
2F
CRC: high order byte
8A
Field:
Example (hex):
SLAVE ADDRESS
11
response message from slave 11
FUNCTION CODE
10
store multiple setpoint values
DATA STARTING ADDRESS: high order byte
11
data starting at address 0180
DATA STARTING ADDRESS: low order byte
80
NUMBER OF SETPOINTS: high order byte
00
6 setpoint values = 12 bytes total
NUMBER OF SETPOINTS: low order byte
06
CRC: low order byte
42
CRC: high order byte
8F
Master Query Message:
Example (hex):
SLAVE ADDRESS
11
query message for slave 11
FUNCTION CODE
03
read register values
DATA STARTING ADDRESS: high order byte
01
data starting at address 0100
DATA STARTING ADDRESS: low order byte
00
NUMBER OF REGISTERS: high order byte
00
6 setpoint values = 12 bytes total
NUMBER OF REGISTERS: low order byte
06
CRC: low order byte
C6
CRC: high order byte
A4
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...