GE Power Management
745 Transformer Management Relay
1-5
1 PRODUCT OVERVIEW
1.2 TECHNICAL SPECIFICATIONS
1
1.2 TECHNICAL SPECIFICATIONS
1.2.1 APPLICABILITY
Transformers:
2 Winding or 3 Winding
Frequency:
50 or 60 Hz nominal
(frequency tracking allows operation from 2 to 65 Hz)
1.2.2 INPUTS
CONTROL POWER (POWER SUPPLY)
Options:
LO/HI (specified when ordering)
LO Range:
DC = 20 to 60 V; AC = 20 to 48 V @ 48 to 62 Hz
HI Range:
DC = 90 to 300 V; AC = 70 to 265 V @ 48 to 62 Hz
Power:
30 VA nominal, 40 VA maximum
Fuse (not accessible):
Hi-Volt:
Current rating: 3.15 A
Type: 5
×
20 mm Slow-Blow Littelfuse, High Breaking Capacity
Model #: 2153.15
Low-Volt:
Current rating: 3.15 A
Type: 5
×
20 mm Slow-Blow Littelfuse, High Breaking Capacity
Model #: 2153.15
PHASE CURRENT INPUT
Source CT:
1 to 50000 A primary / 1 or 5 A secondary
Relay Input:
1 A or 5 A (specified when ordering)
Burden:
Less than 0.2 VA at rated load per phase
Conversion Range:
0.02 to 46
×
CT
Accuracy:
at
<
4 x CT:
± 0.25% of 4
×
CT (± 0.01
×
CT)
at
≥
4 x CT:
± 0.5% of 46
×
CT (± 0.2
×
CT)
Overload Withstand:
1 second at 80 times rated current
2 seconds at 40 times rated current
continuous at 3 times rated current
GROUND CURRENT INPUT
Source CT:
1 to 50000 A primary / 1 or 5 A secondary
Relay Input:
1 A or 5 A (specified when ordering)
Burden:
Less than 0.2 VA at rated load
Conversion Range:
0.02 to 46
×
CT
Accuracy:
at
<
4
×
CT: ± 0.25% of 4 x CT (± 0.01
×
CT)
at
≥
4
×
CT: ± 0.5% of 46 x CT (± 0.2
×
CT)
Overload Withstand:
1 second at 80 times rated current
2 seconds at 40 times rated current
continuous at 3 times rated current
VOLTAGE INPUTS
Source VT:
2 to 600 kV / 60 to 120 V
Source VT Ratio:
1 to 5000 in steps of 1
Relay Input:
60 V to 120 V phase-neutral
Burden:
Less than 0.025 VA at 120 V
Max. Continuous:
273 V
Accuracy:
± 1% of 2
×
VT (± 0.02
×
VT)
LOGIC INPUTS (16)
Dry Contacts:
1000
Ω
maximum ON resistance (32 V DC at 2 mA provided by 745)
Wet Contacts:
Inputs 1 to 16: 30 to 300 V DC at 1.5 mA
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...