4 FRONT PANEL OPERATION
4.2 DISPLAY, INDICATORS, AND FRONT PORT
4
d) DIFFERENTIAL BLOCKED
The DIFFERENTIAL BLOCKED indicator is on when the restrained differential protection feature is enabled
but is being blocked from operating by any of the harmonic restraint features.
The indicator is on if the following condition is met:
•
S4 ELEMENTS / DIFFERENTIAL / HARMONIC RESTRAINT
is blocking any phase (see scheme logic)
e) LOCAL
The LOCAL indicator is on when the 745 is in local mode, i.e. the front panel RESET key is operational.
f) MESSAGE
The MESSAGE indicator is on when any element has picked up, operated, or is now in a latched state waiting
to be reset. With this indicator on, the front panel display is sequentially displaying information about each ele-
ment that has detected an abnormal condition.
4.2.4 SYSTEM STATUS INDICATORS
a) TRANSFORMER DE-ENERGIZED
The TRANSFORMER DE-ENERGIZED indicator is on when the energization inhibit
feature has detected that the transformer is de-energized.
The indicator is on if the
S4 ELEMENTS/DIFFERENTIAL/ENERGIZATN INHIBIT
feature is
detecting the transformer as de-energized
b) TRANSFORMER OVERLOAD
The TRANSFORMER OVERLOAD indicator is on when
S4 ELEMENTS/XFORMER
OVERLOAD
has operated.
c) LOAD-LIMIT REDUCED
The LOAD-LIMIT REDUCED indicator is on when the adaptive harmonic factor cor-
rection feature is detecting enough harmonic content to reduce the load rating of the
transformer. The indicator is on if
S2 SYSTEM SETUP/HARMONIC DERATING/HARMONIC
DERATING ESTIMATION
is
Enabled
and the harmonic derating function is below 0.96.
d) SETPOINT GROUP 1
The SETPOINT GROUP 1 indicator is on when the active setpoint group is 1. This indicator flashes when this
setpoint group is being edited.
e) SETPOINT GROUP 2
The SETPOINT GROUP 2 indicator is on when the active setpoint group is 2. This indicator flashes when this
setpoint group is being edited.
f) SETPOINT GROUP 3
The SETPOINT GROUP 3 indicator is on when the active setpoint group is 3. This indicator flashes when this
setpoint group is being edited.
g) SETPOINT GROUP 4
The SETPOINT GROUP 4 indicator is on when the active setpoint group is 4. This indicator flashes when this
setpoint group is being edited.
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...