5-92
745 Transformer Management Relay
GE Power Management
5.9 TIME OVERCURRENT CURVES
5 SETPOINTS
5
Table 5–11: ANSI CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
M
CURRENT
I
/
I
pkp
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
ANSI EXTREMELY INVERSE
0.5
2.000
0.872
0.330
0.184
0.124
0.093
0.075
0.063
0.055
0.049
1.0
4.001
1.744
0.659
0.368
0.247
0.185
0.149
0.126
0.110
0.098
2.0
8.002
3.489
1.319
0.736
0.495
0.371
0.298
0.251
0.219
0.196
4.0
16.004
6.977
2.638
1.472
0.990
0.742
0.596
0.503
0.439
0.393
6.0
24.005
10.466
3.956
2.208
1.484
1.113
0.894
0.754
0.658
0.589
8.0
32.007
13.955
5.275
2.944
1.979
1.483
1.192
1.006
0.878
0.786
10.0
40.009
17.443
6.594
3.680
2.474
1.854
1.491
1.257
1.097
0.982
ANSI VERY INVERSE
0.5
1.567
0.663
0.268
0.171
0.130
0.108
0.094
0.085
0.078
0.073
1.0
3.134
1.325
0.537
0.341
0.260
0.216
0.189
0.170
0.156
0.146
2.0
6.268
2.650
1.074
0.682
0.520
0.432
0.378
0.340
0.312
0.291
4.0
12.537
5.301
2.148
1.365
1.040
0.864
0.755
0.680
0.625
0.583
6.0
18.805
7.951
3.221
2.047
1.559
1.297
1.133
1.020
0.937
0.874
8.0
25.073
10.602
4.295
2.730
2.079
1.729
1.510
1.360
1.250
1.165
10.0
31.341
13.252
5.369
3.412
2.599
2.161
1.888
1.700
1.562
1.457
ANSI NORMALLY INVERSE
0.5
2.142
0.883
0.377
0.256
0.203
0.172
0.151
0.135
0.123
0.113
1.0
4.284
1.766
0.754
0.513
0.407
0.344
0.302
0.270
0.246
0.226
2.0
8.568
3.531
1.508
1.025
0.814
0.689
0.604
0.541
0.492
0.452
4.0
17.137
7.062
3.016
2.051
1.627
1.378
1.208
1.082
0.983
0.904
6.0
25.705
10.594
4.524
3.076
2.441
2.067
1.812
1.622
1.475
1.356
8.0
34.274
14.125
6.031
4.102
3.254
2.756
2.415
2.163
1.967
1.808
10.0
42.842
17.656
7.539
5.127
4.068
3.445
3.019
2.704
2.458
2.260
ANSI MODERATELY INVERSE
0.5
0.675
0.379
0.239
0.191
0.166
0.151
0.141
0.133
0.128
0.123
1.0
1.351
0.757
0.478
0.382
0.332
0.302
0.281
0.267
0.255
0.247
2.0
2.702
1.515
0.955
0.764
0.665
0.604
0.563
0.533
0.511
0.493
4.0
5.404
3.030
1.910
1.527
1.329
1.208
1.126
1.066
1.021
0.986
6.0
8.106
4.544
2.866
2.291
1.994
1.812
1.689
1.600
1.532
1.479
8.0
10.807
6.059
3.821
3.054
2.659
2.416
2.252
2.133
2.043
1.972
10.0
13.509
7.574
4.776
3.818
3.324
3.020
2.815
2.666
2.554
2.465
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...