11-6
745 Transformer Management Relay
GE Power Management
11.1 COMMISSIONING SUMMARY
11 SETPOINT TABLES
11
11.1.5 S4 ELEMENTS
Table 11–5: S4 ELEMENTS SETPOINT GROUPS
SETPOINT GROUP
DEFAULT
USER VALUE
ACTIVE SETPOINT GROUP
Group 1
EDIT SETPOINT GROUP
Active
GROUP 2 ACTIVATE SIGNAL
Disabled
GROUP 3 ACTIVATE SIGNAL
Disabled
GROUP 4 ACTIVATE SIGNAL
Disabled
Table 11–6: S4 ELEMENTS (Sheet 1 of 12)
DESCRIPTION
DEFAULT
GROUP 1
GROUP 2
GROUP 3
GROUP 4
DIFFERENTIAL
Percent Differential Function
Enabled
Percent Differential Target
Latched
Percent Differential Pickup
0.30 x CT
Percent Differential Slope 1
25%
Percent Differential Kneepoint
2.0 x CT
Percent Differential Slope 2
100%
Percent Differential Block
Disabled
Harmonic Inhibit Function
Enabled
Harmonic Inhibit Parameters
2nd
Harmonic Avg
Disabled
Harmonic Inhibit Level
20.0% ƒo
Energization Function
Enabled
Energization Parameters
2nd
Harmonic Avg
Enabled
Energization Level
20.0% ƒo
Energization Duration
0.10 s
Energization Current Sensing
Enabled
Energization Min. Current
0.10 x CT
Energization Voltage Sensing
Disabled
Energization Min. Voltage
0.85 x VT
Brkrs Open Signal
Disabled
Parallel Xfmr Brkr
Disabled
5th Harmonic Inhibit Function
Disabled
Harmonic Avg
Disabled
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...