GE Power Management
745 Transformer Management Relay
5-89
5 SETPOINTS
5.8 S6 TESTING
5
5.8.5 PREFAULT VALUES
This section contains the settings to configure prefault mode simulation.
Table 5–9: SIMULATION MODES
MODE
DESCRIPTION
Prefault Mode
Select
Prefault Mode
to simulate the normal operating condition of a transformer. In this
mode, the normal inputs are replaced with sample values generated based on the
programmed prefault values. Phase currents are balanced (i.e. equal in magnitude and
120
°
apart), and the phase lag between windings is that which would result under normal
conditions for the transformer type selected. The magnitude of phase currents for each
winding are set to the values programmed in
S6 TESTING/SIMULATION/PREFAULT VALUES/W1
(2/3) PHASE ABC CURRENT MAGNITUDE
. The magnitude of the voltage is set to the value
programmed in
S6 TESTING/SIMULATION/PREFAULT VALUES/VOLTAGE INPUT MAGNITUDE
. The
frequency is set to the value programmed in
S2 SYSTEM SETUP/TRANSFORMER/NOMINAL
FREQUENCY
.
Fault Mode
Select
Fault Mode
to simulate the faulted operating condition of a transformer. In this mode,
the normal inputs are replaced with sample values generated based on the programmed
fault values. The magnitude and angle of each phase current and ground current of the
available windings, the magnitude and angle of the voltage input, and system frequency
are set to the values programmed under
S6 TESTING/SIMULATION/FAULT VALUES
.
A logic input, programmed to the
Simulate Fault
function, can be used to trigger the
transition from the
Prefault Mode
to the
Fault Mode
, allowing the measurement of element
operating times.
Playback Mode Select
Playback Mode
to play back a sampled waveform data file which has been pre-loaded
into the relay. In this mode, the normal inputs are replaced with 16-cycles of waveform
samples downloaded into the 745 by the 745PC program (from an oscillographic data file
in the IEEE “Comtrade” file format).
A logic input, programmed to the
Simulate Playback
function, can be used to trigger the
transition from the
Prefault Mode
to the
Playback Mode
, allowing the measurement of
element operating times.
y
PREFAULT VALUES
y
[ENTER] for more
This message indicates the start of the
PREFAULT VALUES
section. To
continue these setpoints press
or press
for the next section.
W1 PHASE ABC CURRENT
MAGNITUDE: 1.0 x CT
Range: 0.0 to 40.0 (steps of 0.1)
Enter the winding 1 (2/3) phase current magnitude (in terms of the winding
full load current) while in
Prefault Mode
.
VOLTAGE INPUT
MAGNITUDE: 1.0 x VT
Range: 0.0 to 2.0 (steps of 0.1)
Enter the voltage magnitude (in terms of the nominal VT secondary voltage)
while in
Prefault Mode
.
E N TE R
M E SS A G E
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...