1-6
745 Transformer Management Relay
GE Power Management
1.2 TECHNICAL SPECIFICATIONS
1 PRODUCT OVERVIEW
1
ANALOG INPUT
Type:
DC mA
Ranges:
0-1 mA, 0-5 mA, 0-10 mA, 0-20 mA, or 4-20 mA (programmable)
Input Impedance:
375
Ω
± 10%
Conversion Range:
0 to 21 mA
Accuracy:
± 1% of full scale (based on input range)
TAP POSITION
Type:
resistance (ohms)
Range:
0 to 500
Ω
or 0.5 to 5.0 k
Ω
Bias Current:
1 mA or 10 mA (based on input range)
Accuracy:
± 1% of full scale (based on input range)
RTD
Type:
3 wire
RTD Type
100
Ω
Platinum (DIN.43760)
100
Ω
Nickel
120
Ω
Nickel
IRIG-B INPUT
Amplitude-Modulated:
1.0 to 10 V pk-pk
DC Shift:
TTL
Input Impedance
70 to 100 k
Ω
1.2.3 PROTECTION ELEMENTS
PERCENT DIFFERENTIAL PROTECTION
Operating Current Pickup:
0.05 to 1.00 in steps of 0.01 x CT
Dropout Level:
97 to 98% of Pickup
SLOPE-1 Range:
15% to 100% in steps of 1
SLOPE-2 Range:
50% to 200% in steps of 1
KP (SLOPE-1 Kneepoint):
1.0 to 20.0 in steps of 0.1 x CT
Harmonic Restraint:
0.1% to 65.0% in steps of 0.1
Operate Time:
Solid State Output: Pickup < 1 x CT: 42 to 52 ms
1 x CT < Pickup < 1.1
×
kneepoint: 34 to 44 ms
Pickup > 1.1
×
kneepoint: 26 to 36 ms
Relay Outputs 2-5: Pickup < 1 x CT: 46 to 56 ms
1 x CT < Pickup < 1.1
×
kneepoint: 38 to 48 ms
Pickup > 1.1
×
kneepoint: 30 to 40 ms
INSTANTANEOUS DIFFERENTIAL OVERCURRENT
Pickup Level:
3.00 to 20.00 in steps of 0.01 x CT
Dropout Level:
97 to 98% of Pickup
Level Accuracy:
Per current input
Operate Time:
Solid State Output: at 1.2 x pickup: 22 to 30 ms
at 2.0 x pickup: 18 to 26 ms
at 4.0 x pickup:11 to 19 ms
Relay Outputs 2-5: at 1.2 x pickup: 28 to 36 ms
at 2.0 x pickup: 24 to 32 ms
at 4.0 x pickup: 17 to 25 ms
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...