5-78
745 Transformer Management Relay
GE Power Management
5.6 S4 ELEMENTS
5 SETPOINTS
5
5.6.19 TRANSFORMER OVERLOAD
This section contains the settings to configure the transformer overload monitoring element.
y
XFORMER OVERLOAD
y
[ENTER] for more
This message indicates the start of the
TRANSFORMER OVERLOAD
section. To
continue these setpoints press
or press
for the next section.
TRANSFORMER OVERLOAD
FUNCTION: Disabled
Range: Disabled / Enabled
TRANSFORMER OVERLOAD
TARGET: Self-reset
Range: Self-reset / Latched / None
Select
None
to inhibit the display of the target message when the element
operates. Thus an element whose “target type” is
None
never disables the
LED self-test feature since it cannot generate a displayable target message.
TRANSFORMER OVERLOAD
PICKUP: 208% rated
Range: 50 to 300 (steps of 1)
Enter the transformer loading (in terms of the percent of rated load) above
which the transformer overload element will pickup and start the delay timer.
TRANSFORMER OVERLOAD
DELAY: 10 s
Range: 0 to 60000 (steps of 1)
Enter the time that the transformer loading must remain above the pickup
level before the element operates.
TRANSFORMER OVERLOAD
BLOCK: Disabled
Range: Disabled / Logc Inpt 1 (2-16) /Virt Inpt 1 (2-16) / Output Rly 1 (2-8) /
SelfTest Rly / Virt Outpt 1 (2-5)
XFMR OVERTEMP ALARM
SIGNAL: Disabled
Range: Disabled / Logc Inpt 1 (2-16)
Select any logic input that, when asserted, indicates the transformer cooling
system has failed and an over-temperature condition exists. The logic input
should be connected to the transformer winding temperature alarm contacts.
E N T E R
M E SSA G E
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...