GE Power Management
745 Transformer Management Relay
8-67
8 COMMUNICATIONS
8.3 MODBUS MEMORY MAP
8
FACTORY
SERVICE
continued
5004
Force LED Status Column 3
---
---
---
F54
0
5005
Force Other Hardware
---
---
---
F72
0
5006
Reserved
↓
↓
↓
↓
↓
↓
↓
5009
Reserved
SETTING
ERRORS
500A
FlexLogic Equation Error
---
---
---
F76
0 = None
500B
Bad Transformer Settings Error
---
---
---
F77
0 = None
500C
Reserved
↓
↓
↓
↓
↓
↓
↓
500F
Reserved
SELF-TEST
ERROR
FLAGS
5010
Logic Input Error Flag
---
---
---
F52
0
5011
Analog Output Error Flag
---
---
---
F52
0
5012
Calibration Error Flag
---
---
---
F52
0
5013
EEPROM Error Flag
---
---
---
F52
0
5014
Real Time Clock Error Flag
---
---
---
F52
0
5015
Battery Error Flag
---
---
---
F52
0
5016
Emulation Software Error Flag
---
---
---
F52
0
5017
Internal Temperature Error Flag
---
---
---
F52
0
5018
Flexlogic Error Flag
---
---
---
F52
0
5019
DSP Error Flag
---
---
---
F52
0
501A
Bad Settings Error Flag
---
---
---
F52
0
501B
IRIG-B Signal Error Flag
---
---
---
F52
0
501C
Access Denied Error Flag
---
---
---
F52
0
501D
Ambient Temperature Error Flag
---
---
---
F52
---
501E
Reserved
↓
↓
↓
↓
↓
↓
↓
501F
Reserved
HARDWARE
DIAGNOSTICS
5020
Operating Hours of Relay
0 to 65535
1
hours
F1
0
5021
Internal Temperature
–55.0 to 150.0
0.1
° C
F5
---
5022
Minimum Internal Temperature
–55.0 to 150.0
0.1
° C
F5
---
5023
Maximum Internal Temperature
–55.0 to 150.0
0.1
° C
F5
---
5024
0-1 mA Analog Input
0 to 65535
1
µA
F1
---
5025
0-20 mA Analog Input
0 to 65535
1
µA
F1
---
5026
Last Front Panel Key Pressed
---
---
---
F55
00 h = No Key
5027
DSP Diagnostic Flags
---
---
---
F51
---
5028
Reserved
↓
↓
↓
↓
↓
↓
↓
502F
Reserved
Table 8–6: 745 MEMORY MAP (Sheet 51 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...