GE Power Management
745 Transformer Management Relay
5-67
5 SETPOINTS
5.6 S4 ELEMENTS
5
c) OVERFREQUENCY
y
OVERFREQUENCY
y
[ENTER] for more
This message indicates the start of the
OVERFREQUENCY
section. To continue
these setpoints press
or press
for the next section.
OVERFREQUENCY
FUNCTION: Disabled
Range: Disabled / Enabled
OVERFREQUENCY
TARGET: Latched
Range: Self-reset / Latched / None
Select
None
to inhibit the display of the target message when the element
operates. Thus an element whose “target type” is
None
will never disable the
LED self-test feature because it cannot generate a displayable target
message.
CURRENT SENSING:
Enabled
Range: Disabled / Enabled
MINIMUM OPERATING
CURRENT: 0.20 x CT
Range: 0.20 to 1.00 (steps of 0.01)
Enter the minimum value of Winding 1 phase A current (in units of relay
nominal current) required to allow the overfrequency element to operate.
MINIMUM OPERATING
VOLTAGE: 0.50 x VT
Range: 0.10 to 0.99 (steps of 0.01)
Enter the minimum value of voltage (in units of relay nominal voltage)
required to allow the underfrequency element to operate.
OVERFREQUENCY
PICKUP: 60.50 Hz
Range: 50.01 to 65.00 (steps of 0.01)
Enter the frequency (in Hz) above which the overfrequency element will
pickup and start the delay timer.
OVERFREQUENCY
DELAY: 5.00 s
Range: 0.00 to 600.00 (steps of 0.05)
Enter the time that the frequency must remain above the pickup level before
the element operates.
OVERFREQUENCY
BLOCK: Disabled
Range: Disabled / Logc Inpt 1 (2-16) /Virt Inpt 1 (2-16) / Output Rly 1 (2-8) /
SelfTest Rly / Virt Outpt 1 (2-5)
EN TE R
M E SSA G E
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...