GE Power Management
745 Transformer Management Relay
5-39
5 SETPOINTS
5.4 S2 SYSTEM SETUP
5
5.4.8 AMBIENT TEMPERATURE
The 745 provides an RTD input for monitoring the ambient temperature. The three RTD types which may be
used are 100
Ω
platinum, 120
Ω
nickel, and 100
Ω
nickel, the characteristics of which are as follows:
There is a display for each month similar to the box above.
Table 5–4: RTD RESISTANCE VS. TEMPERATURE
Temperature
(° Celsius)
100
Ω
Platinum
(DIN 43760)
120
Ω
Nickel
100
Ω
Nickel
Temperature
(° Celsius)
100
Ω
Platinum
(DIN 43760)
120
Ω
Nickel
100
Ω
Nickel
–50
80.31
86.17
71.81
110
142.29
209.85
174.87
–40
84.27
92.76
77.30
120
146.06
219.29
182.75
–30
88.22
99.41
82.84
130
149.82
228.96
190.80
–20
92.16
106.15
88.45
140
153.58
238.85
199.04
–10
96.09
113.00
94.17
150
157.32
248.95
207.45
0
100.00
120.00
100.00
160
161.04
259.30
216.08
10
103.90
127.17
105.97
170
164.76
269.91
224.92
20
107.79
134.52
112.10
180
168.47
280.77
233.97
30
111.67
142.06
118.38
190
172.46
291.96
243.30
40
115.54
149.79
124.82
200
175.84
303.46
252.88
50
119.39
157.74
131.45
210
179.51
315.31
262.76
60
123.24
165.90
138.25
220
183.17
327.54
272.94
70
127.07
174.25
145.20
230
186.82
340.14
283.45
80
130.89
182.84
152.37
240
190.45
353.14
294.28
90
134.70
191.64
159.70
250
194.08
366.53
305.44
100
138.50
200.64
167.20
y
AMBIENT TEMP
y
[ENTER] for more
This message indicates the start of the
AMBIENT TEMP
section. To continue
these setpoints press
, or press
to go to the next section.
AMBIENT TEMPERATURE
SENSING: Disabled
Range: Disabled / Enabled
Enter
Enabled
to use an RTD to monitor ambient temperature.
AMBIENT RTD TYPE:
100
Ω
Platinum
Range: 100
Ω
Platinum / 120
Ω
Nickel / 100
Ω
Nickel / By Monthly Average
Enter the RTD sensor type being used.
AVERAGE AMBIENT TEMP
FOR JANUARY:
20ºC
Range: –50ºC to 125ºC (steps)
This message is displayed only when the
AMBIENT RTD TYPE
is set for
By
Monthly Average
. Ambient temperature is used in the calculation of Insulation
Aging and must be enabled for the function to operate.
EN TE R
M E SS A G E
NOTE
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...