GE Power Management
745 Transformer Management Relay
8-49
8 COMMUNICATIONS
8.3 MODBUS MEMORY MAP
8
1E1F
Reserved
SIMULATION
SETUP
1E20
Simulation Function
---
---
---
F48
0 = Disabled
1E21
Block Operation of Outputs
---
---
---
F67
255 = 12345678
1E22
Start Fault Mode Signal
---
---
---
F88
0 = Disabled
1E23
Start Playback Mode Signal
---
---
---
F88
0 = Disabled
1E24
Reserved
↓
↓
↓
↓
↓
↓
↓
1E27
Reserved
SIMULATION
PREFAULT
VALUES
1E28
Prefault Wdg 1 Phase ABC Current Magnitudes
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E29
Prefault Wdg 2 Phase ABC Current Magnitudes
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E2A
Prefault Wdg 3 Phase ABC Current Magnitudes
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E2B
Prefault Voltage Input Magnitude
0.0 to 2.0
0.1
×
VT
F2
10 = 1.0
×
VT
1E2C
Reserved
↓
↓
↓
↓
↓
↓
↓
1E2F
Reserved
SIMULATION
FAULT VALUES
1E30
Fault Winding 1 Phase A Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E31
Fault Winding 1 Phase A Current Angle
---
---
°
F1
0°
1E32
Fault Winding 1 Phase B Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E33
Fault Winding 1 Phase B Current Angle
0 to 359
1
° Lag
F1
120° Lag
1E34
Fault Winding 1 Phase C Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E35
Fault Winding 1 Phase C Current Angle
0 to 359
1
° Lag
F1
240° Lag
1E36
Fault Winding 1 Ground Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
0.0 x CT
1E37
Fault Winding 1 Ground Current Angle
0 to 359
1
° Lag
F1
0° Lag
1E38
Fault Winding 2 Phase A Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E39
Fault Winding 2 Phase A Current Angle
0 to 359
1
° Lag
F1
0° Lag
1E3A
Fault Winding 2 Phase B Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E3B
Fault Winding 2 Phase B Current Angle
0 to 359
1
° Lag
F1
120° Lag
1E3C
Fault Winding 2 Phase C Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E3D
Fault Winding 2 Phase C Current Angle
0 to 359
1
° Lag
F1
240° Lag
1E3E
Fault Winding 2 Ground Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
0.0
×
CT
1E3F
Fault Winding 2 Ground Current Angle
0 to 359
1
° Lag
F1
0° Lag
1E40
Fault Winding 3 Phase A Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E41
Fault Winding 3 Phase A Current Angle
0 to 359
1
° Lag
F1
330° Lag
1E42
Fault Winding 3 Phase B Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E43
Fault Winding 3 Phase B Current Angle
0 to 359
1
° Lag
F1
90° Lag
1E44
Fault Winding 3 Phase C Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E45
Fault Winding 3 Phase C Current Angle
0 to 359
1
° Lag
F1
210° Lag
1E46
Fault Winding 3 Ground Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
0.0
×
CT
Table 8–6: 745 MEMORY MAP (Sheet 33 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...