10-12
745 Transformer Management Relay
GE Power Management
10.5 DISPLAY, METERING, COMMUNICATIONS, ANALOG OUTPUTS
10 COMMISSIONING
10
Refer to RTD tables included in this manual for calibration of resistance versus temperature.
c) AMBIENT TEMPERATURE BY MONTHLY AVERAGES
1.
If the ambient temperature is entered as 12 monthly averages, program the value for the month during
which the relay is being commissioned.
Table 10–1: MEASURED RTD TEMPERATURE – 100
Ω
PLATINUM
100
Ω
PLATINUM
RESISTANCE
EXPECTED RTD READING
MEASURED RTD
TEMPERATURE
____°C ____°F
(select one)
°C
°F
80.31
–50 –58
100.00
0 32
119.39
50 122
138.50
100 212
157.32
150 302
175.84
200 392
194.08
250 482
Table 10–2: MEASURED RTD TEMPERATURE – 120
Ω
NICKEL
120
Ω
NICKEL
RESISTANCE
EXPECTED RTD READING
MEASURED RTD
TEMPERATURE
____°C ____°F
(select one)
°C
°F
86.17
–50 –58
120.0
0 32
157.74
50 122
200.64
100 212
248.95
150 302
303.46
200 392
366.53
250 482
Table 10–3: MEASURED RTD TEMPERATURE – 100
Ω
NICKEL
100
Ω
NICKEL
RESISTANCE
EXPECTED RTD READING
MEASURED RTD
TEMPERATURE
____°C ____°F
(select one)
°C
°F
71.81
–50 –58
100.00
0 32
131.45
50 122
167.20
100 212
207.45
150 302
252.88
200 392
305.44
250 482
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...