8-16
745 Transformer Management Relay
GE Power Management
8.2 MODBUS PROTOCOL
8 COMMUNICATIONS
8
c) FUNCTION CODE 06H SUBSTITUTION
Function code 06h (STORE SINGLE SETPOINT) is simply a shorter version of function code 10h (STORE
MULTIPLE SETPOINTS). Using function code 10h, such that the NUMBER OF SETPOINTS stored is 1, has
the same effect as function code 06h. The message format and example is shown below.
Request slave device 11 to write the single setpoint value 00C8 at setpoint address 1100.
8.2.18 MEMORY MAP ORGANIZATION
Data in the 745 that is accessible via computer communications is grouped into several sections of the mem-
ory map as shown in the table below. All memory map locations are two-byte (16-bit) values. The following
section lists all memory map locations. Addresses for all locations are in hexadecimal. Consult the range, step,
units, and the data format (listed after the memory map) to interpret the register values.
Master Query Message:
Example (hex):
SLAVE ADDRESS
11
query message for slave 11
FUNCTION CODE
10
store multiple setpoints (substituted for code 06H)
DATA STARTING ADDRESS: high order byte
11
data starting at address 1100
DATA STARTING ADDRESS: low order byte
00
NUMBER OF SETPOINTS: high order byte
00
1 setpoint values = 2 bytes total
NUMBER OF SETPOINTS: low order byte
01
BYTE COUNT
02
2 bytes of data
DATA #1: high order byte
00
data for address 1100 = 00C8
DATA #1: low order byte
C8
CRC: low order byte
6B
CRC: high order byte
07
Field:
Example (hex):
SLAVE ADDRESS
11
response message from slave 11
FUNCTION CODE
00
store multiple setpoint values
DATA STARTING ADDRESS: high order byte
11
data starting at address 1100
DATA STARTING ADDRESS: low order byte
00
NUMBER OF SETPOINTS: high order byte
00
1 setpoint values = 2 bytes total
NUMBER OF SETPOINTS: low order byte
01
CRC: low order byte
06
CRC: high order byte
65
Table 8–5: MEMORY MAP ORGANIZATION
MEMORY MAP SECTION
ADDRESS RANGE
DESCRIPTION
Product ID
0000 to 007F
Identification and revision information. Read only.
Commands
0080 to 00FF
Substitute command locations. Read and write.
User Map
0100 to 01FF
User Map Values and Addresses. Read and write.
Actual Values
0200 to 07FF
Read only.
Event Recorder
0800 to 0FFF
Read only (except "Event Record Selector Index").
Common Setpoints
1000 to 1FFF
Read and write.
Setpoint Group 1/2/3/4
2000 to 3FFF
Read and write.
Trace Memory
4000 to 47FF
Read only (except "Trace Buffer Selector Index" and "Trace
Channel Selector Index").
Playback Memory
4800 to 4FFF
Read and write.
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...