8-90
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
F95
16 bits
SIGNED VALUE
AUTORANGING BASED ON
WINDING 3 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Signed value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Signed value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
F96
32 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 1 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Signed value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Signed value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
F97
32 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 2 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Signed value, 3 decimal places
Example: 1.234 stored as 1234
Table 8–7: 745 DATA FORMATS (Sheet 33 of 35)
FORMAT
CODE
APPLICABLE BITS
DEFINITION
For 2 A < CT PRIMARY
≤
20 A
Format: Signed value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
F98
32 bits
UNSIGNED VALUE, AUTORANGING
BASED ON WINDING 3 PHASE CT
PRIMARY
For CT PRIMARY
≤
2 A
Format: Signed value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Signed value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
F99
16 bits
Port used for DNP
0000 0000 0000 0000 0=None
0000 0000 0000 0001 1=Com 1
0000 0000 0000 0010 2=Com 2
0000 0000 0000 0011 3=Front
F100
16 bits
Cooling Type For Dry Transformer
0000 0000 0000 0000 0=Sealed Self Cooled
0000 0000 0000 0001 1=Vented Self cooled
0000 0000 0000 0010 2=Forced-cooled
F101
16 bits
Unsigned value, Autoranging Load
Loss at Rated Load
Low Volt. Winding rating
≥
5 KV
Unsigned Value, 0 Decimal Places
Example: 1234 stored as 1234
1 KV
≤
Low Volt. Winding rating < 5 KV
Unsigned Value, 1 Decimal Place
Example: 123.4 stored as 1234
Low Volt. Winding rating < 1 KV
Unsigned Value, 2 Decimal Places
Example: 12.34 stored as 1234)
Table 8–7: 745 DATA FORMATS (Sheet 34 of 35)
FORMAT
CODE
APPLICABLE BITS
DEFINITION
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...