084F
Event XX Winding 2 Phase B 5th Harmonic
0.0 to 99.9
0.1
% ƒo
F2
0% ƒo
0850
Event XX Winding 2 Phase C 5th Harmonic
0.0 to 99.9
0.1
% ƒo
F2
0% ƒo
0851
Event XX Winding 3 Phase A Current Magnitude
---
---
A
F80
0 A
0852
Event XX Winding 3 Phase A Current Angle
0 to 359
1
° Lag
F1
0° Lag
0853
Event XX Winding 3 Phase B Current Magnitude
---
---
A
F80
0 A
0854
Event XX Winding 3 Phase B Current Angle
0 to 359
1
° Lag
F1
0° Lag
0855
Event XX Winding 3 Phase C Current Magnitude
---
---
A
F80
0 A
0856
Event XX Winding 3 Phase C Current Angle
0 to 359
1
° Lag
F1
0° Lag
0857
Event XX Winding 3 Ground Current Magnitude
---
---
A
F83
0 A
0858
Event XX Winding 3 Ground Current Angle
0 to 359
1
° Lag
F1
0° Lag
0859
Event XX Winding 3 Phase A 2nd Harmonic
0.0 to 99.9
0.1
% ƒo
F2
0% ƒo
085A
Event XX Winding 3 Phase B 2nd Harmonic
0.0 to 99.9
0.1
% ƒo
F2
0% ƒo
085B
Event XX Winding 3 Phase C 2nd Harmonic
0.0 to 99.9
0.1
% ƒo
F2
0% ƒo
085C
Event XX Winding 3 Phase A 5th Harmonic
0.0 to 99.9
0.1
% ƒo
F2
0% ƒo
085D
Event XX Winding 3 Phase B 5th Harmonic
0.0 to 99.9
0.1
% ƒo
F2
0% ƒo
085E
Event XX Winding 3 Phase C 5th Harmonic
0.0 to 99.9
0.1
% ƒo
F2
0% ƒo
085F
Event XX Phase A Differential Current
0.00 to 655.35
0.01
×
CT
F3
0.00
×
CT
0860
Event XX Phase B Differential Current
0.00 to 655.35
0.01
×
CT
F3
0.00
×
CT
0861
Event XX Phase C Differential Current
0.00 to 655.35
0.01
×
CT
F3
0.00
×
CT
0862
Event XX Phase A Restraint Current
0.00 to 655.35
0.01
×
CT
F3
0.00
×
CT
0863
Event XX Phase B Restraint Current
0.00 to 655.35
0.01
×
CT
F3
0.00
×
CT
0864
Event XX Phase C Restraint Current
0.00 to 655.35
0.01
×
CT
F3
0.00
×
CT
0865
Event XX System Frequency
0.00 to 99.99
0.01
Hz
F3
0.00 Hz
0866
Event XX Frequency Decay Rate
–9.99 to 9.99
0.01
Hz/s
F6
0.00 Hz/s
0867
Event XX Tap Changer Position
1 to 50
1
---
F1
0 = n/a
0868
Event XX Volts-per-Hertz
0.00 to 4.00
0.01
V/Hz
F3
0.00 V/Hz
0869
Event XX Ambient Temperature
–51 to 251
1
°C
F4
0 °C
086A
Event XX Analog Input
0 to 65000
1
<Units>
F1
0 <Units>
086B
Reserved
↓
↓
↓
↓
↓
↓
↓
0FFF
Reserved
Common Setpoints (Addresses 1000 to 1FFF) - Read / Write
745 SETUP
1000
745 Setpoints
---
---
---
F29
0 = Not Prog’d
1001
Encrypted Passcode (4 registers) [read only]
---
---
---
F33
"AIKFBAIK"
1005
Beeper
---
---
---
F30
1 = Enabled
1006
Flash Message Time
0.5 to 10.0
0.5
s
F2
40 = 4.0 s
1007
Default Message Timeout
10 to 900
1
s
F1
300 s
1008
Default Message Intensity
0 to 100
25
%
F1
25%
Table 8–6: 745 MEMORY MAP (Sheet 18 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...