5-42
745 Transformer Management Relay
GE Power Management
5.4 S2 SYSTEM SETUP
5 SETPOINTS
5
5.4.11 ANALOG OUTPUTS
There are seven analog outputs on the 745 relay which are selected to provide a full-scale output range of one
of 0-1 mA, 0-5 mA, 4-20 mA, 0-20 mA or 0-10 mA. Each channel can be programmed to monitor any mea-
sured parameter. This sub-section is only displayed with the option installed.
y
ANALOG OUTPUTS
y
[ENTER] for more
This message indicates the start of the
ANALOG OUTPUTS
section. To continue
with these setpoints press
, or press
to go to the next
section.
y
ANALOG OUTPUT 1
y
[ENTER] for more
This message indicates the start of the analog output 1 (2-7) setpoints of the
analog outputs. To continue with these setpoints, press
, or press
to go to the next section.
ANALOG OUTPUT 1
FUNCTION: Disabled
Range: Disabled / Enabled
This message enables or disables the analog output 1 (2-7) feature. When
disabled, 0 mA will appear at the corresponding terminal.
ANALOG OUTPUT 1
VALUE: W1
∅
A Current
Range: see below
Select the measured parameter to be represented by the mA DC current
level of analog output 1 (2-7).
W1 (2/3) fA (B/C) Current
Select to monitor the RMS value (at fundamental frequency) of the winding 1 (2/3)
phase A (B/C) current input.
W1 (2/3) Loading
Select to monitor the winding 1 (2/3) load as a percentage of the rated load for that
winding.
W1 (2/3) fA (B/C) THD
Select to monitor the total harmonic distortion in the winding 1 (2/3) phase A (B/C)
current input.
W1 (2/3) Derating
Select to monitor the harmonic derating factor (i.e. the derated transformer
capability while supplying non-sinusoidal load currents) in winding 1 (2/3).
Frequency
Select to monitor the system frequency.
Tap Position
Select to monitor the onload tap changer position.
Voltage
Select to monitor the system voltage as measured from the voltage input.
W1 (2/3) fA (B/C) Demand
Select to monitor the current demand value of the winding 1 (2/3) phase A (B/C)
current input.
Analog Input
Select to monitor the general purpose analog input current.
Max Event W1 (2/3)
Ia (b/c/g)
Select to monitor the maximum captured RMS value (at fundamental frequency) of
the winding 1 (2/3) phase A (phase B / phase C / ground) current input for all events
since the last time the event recorder was cleared.
ANALOG OUTPUT 1
RANGE: 4-20 mA
Range: 0-1 mA / 0-5 mA / 4-20 mA / 0-20 mA / 0-10 mA
Select the full-scale range of output current for analog output 1 (2-7).
ANALOG OUTPUT 1
MIN: 0 A
Range: matches the range of the selected measured parameter.
Enter the value of the selected parameter which corresponds to the
minimum output current of analog output 1 (2-7).
ANALOG OUTPUT 1
MAX: 1000 A
Range: matches the range of the associated actual value
Enter the value of the selected parameter which corresponds to the
maximum output current of analog output 1 (2-7).
EN T E R
M E SS A G E
E N TE R
M E SSA G E
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...