8-64
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
HOTTEST-
SPOT LIMIT
2380
Hottest-spot Limit Function
---
---
---
F30
0 = Disabled
2381
Hottest-spot Limit Target
---
---
---
F46
0 = Self-reset
2382
Hottest-spot Limit Pickup
50 to 300
1
° C
F1
150° C
2383
Hottest-spot Limit Delay
0 to 60000
1
min
F1
10 min
2384
Hottest-spot Limit Block
---
---
---
F87
0 = Disabled
2385
Reserved
↓
↓
↓
↓
↓
↓
↓
238F
Reserved
LOSS-OF-LIFE
LIMIT
2390
Loss-of-Life Limit Function
---
---
---
F30
0 = Disabled
2391
Loss-of-Life Limit Target
---
---
---
F46
0 = Self-reset
2392
Loss-of-Life Limit Pickup
0 to 20000
1
hrs x 10
F1
16000=160000 hrs
2393
Loss-of-Life Limit Block
---
---
---
F87
0 = Disabled
2394
Reserved
↓
↓
↓
↓
↓
↓
↓
239F
Reserved
ANALOG
INPUT
LEVEL 1
23A0
Analog Input Level 1 Function
---
---
---
F30
0 = Disabled
23A1
Analog Input Level 1 Target
---
---
---
F46
0 = Self-reset
23A2
Analog Input Level 1 Pickup
1 to 65000
1
<Units>
F1
10 <Units>
23A3
Analog Input Level 1 Delay
0 to 60000
1
s
F1
50 s
23A4
Analog Input Level 1 Block
---
---
---
F87
0 = Disabled
23A5
Reserved
↓
↓
↓
↓
↓
↓
↓
23AF
Reserved
ANALOG
INPUT
LEVEL 2
23B0
Analog Input Level 2 Function
---
---
---
F30
0 = Disabled
23B1
Analog Input Level 2 Target
---
---
---
F46
0 = Self-reset
23B2
Analog Input Level 2 Pickup
1 to 65000
1
<Units>
F1
100 <Units>
23B3
Analog Input Level 2 Delay
0 to 60000
1
s
F1
100 s
23B4
Analog Input Level 2 Block
---
---
---
F87
0 = Disabled
23B5
Reserved
↓
↓
↓
↓
↓
↓
↓
23BF
Reserved
WINDING 1
CURRENT
DEMAND
23C0
Winding 1 Current Demand Function
---
---
---
F30
0 = Disabled
23C1
Winding 1 Current Demand Target
---
---
---
F46
0 = Self-reset
23C2
Winding 1 Current Demand Pickup
---
---
A
F78
100 A
23C3
Winding 1 Current Demand Block
---
---
---
F87
0 = Disabled
23C4
Reserved
↓
↓
↓
↓
↓
↓
↓
23CF
Reserved
Table 8–6: 745 MEMORY MAP (Sheet 48 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...