8-50
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
SIMULATION
FAULT VALUES
continued
1E47
Fault Winding 3 Ground Current Angle
0 to 359
1
° Lag
F1
0° Lag
1E48
Fault Voltage Input Magnitude
0.0 to 2.0
0.1
×
VT
F2
10 = 1.0
×
VT
1E49
Fault Voltage Input Angle
0 to 359
1
° Lag
F1
0° Lag
1E4A
Fault Frequency
45.00 to 60.00
0.01
Hz
F3
60.00 Hz
1E4B
Reserved
↓
↓
↓
↓
↓
↓
↓
1FFF
Reserved
Setpoint Group 1/2/3/4 (Addresses 2000 to 3FFF) - Read / Write
PERCENT
DIFFERENTIAL
2000
Percent Differential Function
---
---
---
F30
1 = Enabled
2001
Percent Differential Target
---
---
---
F46
1 = Latched
2002
Percent Differential Pickup
0.05 to 1.00
0.01
×
CT
F3
30 = 0.30
×
CT
2003
Percent Differential Slope 1
15 to 100
1
%
F1
25%
2004
Percent Differential Break Point
1.0 to 20.0
0.1
×
CT
F2
20 = 2.0
×
CT
2005
Percent Differential Slope 2
50 to 200
1
%
F1
100%
2006
Percent Differential Block
---
---
---
F87
0 = Disabled
2007
Reserved
HARMONIC
INHIBIT
2008
Harmonic Inhibit Function
---
---
---
F30
1 = Enabled
2009
Harmonic Inhibit Parameters
---
---
---
F64
0 = 2nd
200A
Harmonic Averaging
---
---
---
F30
0 = Disabled
200B
Harmonic Inhibit Level
0.1 to 65.0
0.1
% ƒo
F2
200 = 20.0% ƒ
o
200C
Reserved
ENERGIZATION
INHIBIT
200D
Energization Inhibit Function
---
---
---
F30
1 = Enabled
200E
Energization Inhibit Parameters
---
---
---
F64
0 = 2nd
200F
Harmonic Averaging
---
---
---
F30
1 = Enabled
2010
Energization Inhibit Level
0.1 to 65.0
0.1
% ƒo
F2
200 = 20.0% ƒ
o
2011
Energization Inhibit Duration
0.05 to 600.00
0.01
s
F1
10 = 0.10 s
2012
Energization Sensing By Current
---
---
---
F30
1 = Enabled
2013
Minimum Energization Current
0.10 to 0.50
0.01
×
CT
F3
10 = 0.10
×
CT
2014
Energization Sensing By Voltage
---
---
---
F30
0 = Disabled
2015
Minimum Energization Voltage
0.50 to 0.99
0.01
×
VT
F3
85 = 0.85
×
VT
2016
Breakers Are Open Signal
---
---
---
F88
0 = Disabled
2017
Parallel Transformer Breaker Close Signal
---
---
---
F88
0 = Disabled
2018
Reserved
5TH
HARMONIC
INHIBIT
2019
5th Harmonic Inhibit Function
---
---
---
F30
0 = Disabled
201A
Harmonic Averaging
---
---
---
F30
0 = Disabled
201B
5th Harmonic Inhibit Level
0.1 to 65.0
0.1
% ƒo
F2
100 = 10.0% ƒ
o
201C
Reserved
↓
↓
↓
↓
↓
↓
↓
Table 8–6: 745 MEMORY MAP (Sheet 34 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...