10-10
745 Transformer Management Relay
GE Power Management
10.5 DISPLAY, METERING, COMMUNICATIONS, ANALOG OUTPUTS
10 COMMISSIONING
10
Winding #1: 100 MVA, 220 kV, 250/1 CT ratio (rated current is 262.4 A, hence CT ratio of 250/1)
Winding #2: 100 MVA, 69 kV, 1000/1 CT ratio (rated current is 836.8 A, hence CT ratio of 1000/1)
The 1000/1 CT ratio is not a perfect match for the 250/1 ratio. The high-side CT produces a secondary current
of 262.5/250 = 1.05 A whereas the low-side CT produces a current of 0.837 A. The 745 automatically applies
an amplitude correction factor to the Winding 2 currents to match them to the Winding 1 currents. The following
illustrates how the correction factor is computed:
The mismatch factor is therefore
Winding 2 currents are divided by this factor to obtain balanced conditions for the differential elements.
If this transformer were on line, fully loaded, and protected by a properly set 745 relay, the actual current val-
ues read by the relay would be:
Winding 1: 262.5 A
∠
0° (this is the reference winding)
Winding 2: 836.8 A
∠
210° (30° lag due to transformer and 180° lag due to CT connections)
Differential current: less than 0.03
×
CT as the two winding currents are equal once correctly transformed
inside the relay.
The loading of each winding would be 100% of rated.
The above results can be verified with two adjustable sources of three-phase current. With a single current
source, how the relay performs the necessary phase angle corrections must be taken into account. Table 5–1:
TRANSFORMER TYPES on page 5–10 shows that the Y-side currents are shifted by 30° to match the Delta
secondary side. The 30° phase shift is obtained from the equations below:
By injecting a current into phase A of Winding 1 and phase A of Winding 2 only,
I
W1b
=
I
W1c
= 0 A. Therefore, if
we assume an injected current of 1
×
CT, the
transformed
Y-side currents will be:
For the purposes of the differential elements only
, the transformation has reduced the current to 0.57 times its
original value into phase A, and created an apparent current into phase B, for the described injection condition.
If a 1
×
CT is now injected into phase A Winding 1, the following values for the differential currents for all three
phases should be obtained:
A-phase differential: 0.57
×
CT
∠
0° Lag
B-phase differential: 0.57
×
CT
∠
180° Lag
C-phase: 0
×
CT.
b) EFFECTS OF ZERO-SEQUENCE COMPONENT REMOVAL
The transformation used to obtain the 30° phase shift on the Y-side automatically removes the
zero-sequence current from those signals. The 745 always removes the zero-sequence cur-
rent from the delta winding currents.
If the zero-sequence component is removed from the Delta-side winding currents, the Winding 2 current values
will change under unbalanced conditions. Consider again the case described above, with the 1
×
CT injected
into phase A of Winding 2.
CT
2
ideal
(
)
CT
1
V
1
V
2
------
×
250
1
----------
220 V
69 V
----------------
×
797.1
=
=
=
Ideal CT Ratio
Actual CT Ratio
------------------------------------------
797.1
1000
---------------
0.7971
=
=
I
W1a
′
I
W1a
I
W1c
–
3
-----------------------------
,
I
W1b
′
I
W1b
I
W1a
–
3
-----------------------------
,
I
W1c
′
I
W1c
I
W1b
–
3
-----------------------------
=
=
=
I
W1a
′
1
CT
×
3
-----------------
,
I
W1b
′
1
CT
×
–
3
--------------------
,
I
W1c
′
0
CT
×
3
-----------------
=
=
=
NOTE
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...